Fire Codes for the Congregate Living Facility of no more than 16 total patients!

Table of Contents
1. Presentation Outline
2. Selected CBC Codes
3. SFM Interpretations
4. SFM Information Bulletins
5. Pre-Inspection Form 9290
6. Fire Safety Clearance Form 850, My Home



Unit 1: Introduction
1-1 Orientation and Administration
Unit 2: Residential Care Facilities
  1. 2-1  History .. ...
  2. 2-2  Definitions . . . .......
  3. 2-3  Rolls of Agencies . .. . . .
  4. 2-4  Authority & Responsibility for local enforcement . .
  5. 2-5  Limitations .....
  6. 2-6  Pre-Inspections, Form 9092
  7. 2-7  Fire Safety Clearance, Form 850 ... . . ..
  8. 2-8  R-2.1 Occupancies .
  9. 2-9  R-4 Occupancies . ..
  10. 2-10  R-3.1 Occupancies . ......
  11. 2-11  R-3 Occupancies . ..
  12. 2-12  Existing Occupancies . ..
  13. 2-13  Appeals . ..
  14. 2-14  The Future . .
Unit 3: Class Presentation Evaluation
3-1 Complete the Class Presentation Evaluation........................................................


Selected CBC Sections

CBC 1.11.4.5 Care facilities.
The primary fire enforcing agency shall complete the final fire clearance inspection for a community care facility, residential care facility for the elderly, or child day care facility within 30 days of receipt of the request for the final inspection, or as of the date the prospective facility requests the final pre-licensure inspection by the State Department of Social Services, whichever is later.
Pursuant to Health and Safety Code Section 13235, a fee equal to, but not exceeding the cost of the pre-inspection may be charged for a facility with a capacity to serve 25 or less clients. A fee equal to, but not exceeding the cost of the pre-inspection may be charged for a pre-inspection of a facility with a capacity to serve 26 or more clients.
Pursuant to Health and Safety Code Section 13131.5, a reasonable final inspection fee, not to exceed the actual cost of inspection services necessary to complete a final inspection may be charged for occupancies classified as residential care facilities for the elderly (RCFE).
Pursuant to Health and Safety Code Section 1569.84, neither the State Fire Marshal nor any local public entity shall charge any fee for enforcing fire inspection regulations pursuant to state law or regulation or local ordinance, with respect to residential care facilities for the elderly (RCFE) which service six or fewer persons.
1.11.4.6 Requests of the Office of the State Fire Marshal.
Whenever a local authority having jurisdiction requests that the State Fire Marshal perform plan review and/or inspection services related to a building permit, the applicable fees for such shall be payable to the Office of the State Fire Marshal.
1.11.5 Inspections.
Work performed subject to the provisions of this code shall comply with the inspection requirements of Title 24, Part 2, California Building Standards Code, Appendix Chapter 1, Sections 109.1, 109.3, 109.3.4, 109.3.5, 109.3.6, 109.3.8, 109.3.9, 109.3.10 109.5 and 109.6.
111.5.1 Existing Group I -1 or R occupancies.
Licensed 24-hour care in a Group I-1 or R occupancy in existence and originally classified under previously adopted state codes shall be re-inspected under the appropriate previous code, provided there is no change in the use or character which would place the facility in a different occupancy group.
202 Definitions.

RESTRAINT shall mean the physical retention of a person within a room, cell or holding facility by any means, or within a building by means of locked doors.
SECTION 310 RESIDENTIAL GROUP R
310.1 Residential Group R.
Residential Group R includes, among others, the use of a building or structure, or a portion thereof, for sleeping purposes when not classified as an Institutional Group I. Residential occupancies shall include the following:
R-1 Residential occupancies containing sleeping units where the occupants are primarily transient in nature, including:
Boarding houses (transient)
Hotels (transient)
Motels (transient)
[HCD 1] Efficiency dwelling units (transient)
R-2 Residential occupancies containing sleeping units or more than two dwelling units where the occupants are primarily permanent in nature, including:
Apartment houses
Boarding houses (not transient)
Convents
Dormitories
Fraternities and sororities
Hotels (nontransient)
Monasteries
Motels (nontransient)
Vacation timeshare properties
[HCD 1] Efficiency dwelling units (nontransient)
Congregate living facilities with 16 or fewer occupants are permitted to comply with the construction requirements for Group R-3.

R-2.1 Facilities housing clients on a 24-hour basis in a supervised residential environment that provides personal care services. May contain more than six nonambulatory and/or bedridden clients, including:
Assisted living such as:
Residential care facilities
Residential care facilities for the elderly (RCFE’s)
Adult residential facilities.
Congregate living health facilities.
Group homes.
Residential facilities for the chronically ill.
Congregate living health facilities for the terminally ill. Social rehabilitation facilities such as:
Halfway houses
Community correction reentry centers
Community treatment programs
Work furlough programs
Alcoholism of drug abuse recovery or treatment facilities

R-3 Residential occupancies where the occupants are primarily permanent in nature and not classified as Group R-1, R-2, R-2.1, R-3.1, R-4 or I, including:
Buildings other than townhouses that do not contain more than two dwelling units. Townhouses not more than three stories above grade in height with a separate means of
egress.
Adult care facilities that provide accommodations for clients of any age for less than 24 hours. Licensing categories that may use this classification include, but are not limited to: Adult Day-care Facilities, Adult Day-support Center. [SFM]
Child care facilities that provide accommodations for clients of any age for less than 24 hours. Licensing categories that may use this classification include, but are not limited to: [SFM]
Family Day-care Homes, Day-care Center for Mildly Ill Children, Infant Care Center and School Age Child Day-care Center.
Congregate living facilities with 16 or fewer persons.



R-3.1. [SFM] This occupancy group may include facilities licensed by a governmental agency for a residentially based 24-hour care facility providing accommodations for six or fewer clients of any age. Clients may be classified as ambulatory, non-ambulatory or bedridden. A Group R-3.1 occupancy shall meet the requirements for construction as defined for Group R-3, except as otherwise provided for in Section 425, Special Provisions For Licensed 24-Hour Care Facilities in a Group R-2.1, R-3.1 or R-4 Occupancy. This group may include:
Adult Residential Facilities
page5image18624
Congregate Living Health Facilities
Foster Family Homes
Group Homes
Intermediate Care Facilities for the Developmentally Disabled Habilitative
Intermediate Care Facilities for the Developmentally Disabled Nursing
Nurseries for the full-time care of children under the age of six, but not including “infants” as defined in Section 310
Residential Care Facilities for the Elderly
Small Family Homes and Residential Care Facilities for the Chronically Ill

Exception: Group Homes licensed by the Department of Social Services which provide nonmedical board, room and care for six or fewer ambulatory children or children two years of age or younger, and which do not have any non-ambulatory clients shall not be subject to regulations found in Section 425.
Pursuant to Health and Safety Code Section 13143 with respect to these exempted facilities, no city, county, or public district shall adopt or enforce any requirement for the prevention of fire or for the protection of life and property against fire and panic unless the requirement would be applicable to a structure regardless of the special occupancy. Nothing shall restrict the application of state or local housing standards to such facilities if the standards are applicable to residential occupancies and are not based on the use of the structure as a facility for ambulatory children. For the purpose of this exception, “ambulatory children” does not include relatives of the licensee or the licensee's spouse.
R-4 Residential occupancies shall include buildings arranged for occupancy as residential care/assisted living facilities including more than six ambulatory clients, excluding staff.
Group R-4 occupancies shall meet the requirements for construction as defined for Group R-3, except as otherwise provided for in this code.
This occupancy classification may include a maximum six non-ambulatory or bedridden clients (see Section 425, Special Provisions For Licensed 24-Hour Care Facilities in a Group R-2.1, R-3.1, or R-4 Occupancy). Group R-4 occupancies shall include the following:
Assisted living facilities such as: Residential care facilities, Residential Care Facilities for the Elderly (RCFE's), Adult Residential Facilities, Congregate Living Health facilities, and Group homes.
Social rehabilitation facilities such as: Halfway houses, Community Correctional Centers, Community Correction Reentry Centers, Community Treatment Programs, Work Furlough Programs, and Alcoholism or drug abuse recovery or treatment facilities.
page6image20328 page6image20488

310.2 Definitions.
The following words and terms shall, for the purposes of this section and as used elsewhere in this code, have the meanings shown herein.
AGED HOME OR INSTITUTION [SFM] is a facility used for the housing of persons 65 years of age or older in need of care and supervision. (See definition of “Care and supervision.")
BEDRIDDEN PERSON [SFM] means a person, requiring assistance in turning and repositioning in bed, or being unable to independently transfer to and from bed, except in facilities with appropriate and sufficient care staff, mechanical devices if necessary, and safety precautions as determined in Title 22 regulations, by the Director of Social Services or his or her designated representative.
The Director of Social Services or his or her designated representative shall make the determination of the bedridden status of persons with developmental disabilities, in consultation with the Director of Developmental Services or his or her designated representative.
The Director of Social Services or his or her designated representative shall make the determination of the bedridden status of all other persons with disabilities who are not developmentally disabled.
BOARDING HOUSE. A building arranged or used for lodging for compensation, with or without meals, and not occupied as a single-family unit.
CARE AND SUPERVISION [SFM] means any one or more of the following activities provided by a person or facility to meet the needs of the clients:
Assistance in dressing, grooming, bathing and other personal hygiene.

Assistance with taking medication.
Central storage and/or distribution of medications.
Arrangement of and assistance with medical and dental care.
Maintenance of house rules for the protection of clients.
Supervision of client schedules and activities.
Maintenance and/or supervision of client cash resources or property.
Monitoring of food intake or special diets.
Providing basic services required by applicable law and regulation to be provided by the

Residential Care Facilities Presentation Handout 7 June 1, 2011
licensee in order to obtain and maintain a community-care facility license. CATASTROPHICALLY INJURED, [SFM] as termed, means a person whose origin
of disability was acquired through trauma or non-degenerative neurologic illness, for whom it has been determined by the Department of Health Services Certification and Licensing that active rehabilitation would be beneficial.

CHILD-CARE CENTER [SFM] is any facility of any capacity other than a large or small family day-care home as defined in these regulations in which less than 24-hour-per-day nonmedical supervision is provided for children in a group setting.
CHILD OR CHILDREN [SFM] is a person or persons under the age of 18 years. CHRONICALLY ILL. [B] [SFM] See “Terminally ill.”
CONGREGATE LIVING HEALTH FACILITY (CLHF), [SFM] as termed, is a residential home with a capacity of no more than six beds, which provides inpatient care, including the following basic services: medical supervision, 24-hour skilled nursing and supportive care, pharmacy, dietary, social recreational, and at least provides services for persons who are diagnosed with a terminal illness or who are catastrophically and severely disabled.
CONGREGATE LIVING FACILITIES. A building or part thereof that contains sleeping units where residents share bathroom and/or kitchen facilities.
CONGREGATE RESIDENCE [SFM] is any building or portion thereof that contains facilities for living, sleeping and sanitation, as required by this code, and may include facilities for eating and cooking, for occupancy by other than a family. A congregate residence may be a shelter, convent, monastery, dormitory, fraternity or sorority house, but does not include jails, hospitals, nursing homes, hotels or lodging houses.
DAY CARE [SFM] shall, for the purposes of these regulations, mean the care of persons during any period of a 24-hour day where permanent sleeping accommodations are not provided.
Note: “Day care” shall not be construed to preclude the use of cots or mats for napping purposes, provided all employees, attendants and staff personnel are awake and on duty in the area where napping occurs.
DAY-CARE HOME, LARGE FAMILY [SFM] is a provider’s own home which is licensed to provide day care for periods less than 24 hours per day for nine to 14 persons, including children under the age of 10 years who reside at the home.
DAY-CARE HOME, SMALL FAMILY [SFM] is a home which provides family day care to eight or fewer children, including children under the age of 10 years who reside at the home, in the provider's own home, for periods of less than 24 hours per day. Small-family day-care homes are exempted from state fire and life safety regulations other than those state and local standards applicable to Group R, Division 3 occupancies. [See Health and Safety Code, Section 13143 (b).]
DORMITORY. A space in a building where group sleeping accommodations are provided in
Residential Care Facilities Presentation Handout 8 June 1, 2011
one room, or in a series of closely associated rooms, for persons not members of the same family group, under joint occupancy and single management, as in college dormitories or fraternity houses.
FULL-TIME CARE [B] [SFM] shall mean the establishment and routine care of persons on an hourly, daily, weekly, monthly, yearly or permanent basis, whether for 24 hours per day or less, and where sleeping accommodations are provided.
INFANT, [B] [SFM] for the purpose of these regulations, shall mean any child who because of age only, is unable to walk and requires the aid of another person to evacuate the building. In no case shall the term “infant” mean a child beyond two years of age.
MENTALLY RETARDED PERSONS, PROFOUNDLY OR SEVERELY [B] [SFM] shall mean any retarded person who is unable to evacuate a building unassisted during emergency conditions.
Note: The determination as to such incapacity shall be made by the Director of the State Department of Public Health or his or her designated representative pursuant to Health and Safety Code Section 13131.3.
NON-AMBULATORY PERSONS [B] [SFM] are persons unable to leave a building unassisted under emergency conditions. It includes, but is not limited to, persons who depend on mechanical aids such as crutches, walkers and wheelchairs and any person who is unable to physically and mentally respond to a sensory signal approved by the State Fire Marshal or an oral instruction relating to fire danger.
The determination of ambulatory or non-ambulatory status of persons with developmental disabilities shall be made by the Director of Social Services or his or her designated representative, in consultation with the director of Developmental Services or his or her designated representative. The determination of ambulatory or non-ambulatory status of all other disabled persons placed after January 1, 1984, who are not developmentally disabled shall be made by the Director of Social Services or his or her designated representative.
RESIDENTIAL CARE FACILITY FOR THE CHRONICALLY ILL (RCF/CI) [SFM] as termed, means a housing arrangement with a maximum capacity of 25 residents that provides a range of services to residents who have chronic, life-threatening illnesses.
RESIDENTIAL CARE FACILITY FOR THE ELDERLY (RCFE) [SFM] as defined in Health and Safety Code Section 1569.2, shall mean a facility with a housing arrangement chosen voluntarily by persons 60 years of age or over, or their authorized representative, where varying levels and intensities of care and supervision, protective supervision or personal care are provided, based on their varying needs, as determined in order to be admitted and to remain in the facility. Persons under 60 years of age with compatible needs, as determined by the Department of Social Services in regulations, may be allowed to be admitted or retained in a residential care facility for the elderly.
Pursuant to Health and Safety Code Section 13133, regulations of the state fire marshal pertaining to Group R, Division 2 occupancies classified as Residential Facilities (RF) and Residential Care Facilities for the Elderly (RCFE) shall apply uniformly throughout the state
Residential Care Facilities Presentation Handout 9 June 1, 2011
and no city, county, city and county, including a charter city or charter county, or fire protection district shall adopt or enforce any ordinance or local rule or regulation relating to fire and panic safety which is inconsistent with these regulations. A city, county, city and county, including a charter city or charter county may pursuant to Health and Safety Code Section 13143.5, or a fire protection district may pursuant to Health and Safety Code Section 13869.7, adopt standards more stringent than those adopted by the state fire marshal that are reasonably necessary to accommodate local climate, geological, or topographical conditions relating to roof coverings for Residential-Care Facilities for the Elderly.
RESIDENTIAL FACILITY (RF) [SFM] as defined in Section 1502 of the Health and Safety Code, shall mean any family home, group care facility, or similar facility determined by the director of Social Services, for 24-hour nonmedical care of persons in need of personal services, supervision, or assistance essential for sustaining the activities of daily living or for the protection of the individual. Such facilities include small family homes and social rehabilitation facilities.
Pursuant to Health and Safety Code Section 13133, regulations of the State Fire Marshal pertaining to Group R Occupancies classified as Residential Facilities (RF) and Residential Care Facilities for the Elderly (RCFE) shall apply uniformly throughout the state and no city, county, city and county, including a charter city or charter county, or fire protection district shall adopt or enforce any ordinance or local rule or regulation relating to fire and panic safety which is inconsistent with these regulations. A city, county, city and county, including a charter city or charter county may pursuant to Health and Safety Code Section 13143.5, or a fire protection district may pursuant to Health and Safety Code Section 13869.7, adopt standards more stringent than those adopted by the state fire marshal that are reasonably necessary to accommodate local climate, geological, or topographical conditions relating to roof coverings for Residential Care Facilities for the Elderly.
TERMINALLY ILL [SFM] as termed for an individual, means the individual has a life expectancy of six months or less as stated in writing by his or her attending physician and surgeon.
TRANSIENT. Occupancy of a dwelling unit or sleeping unit for not more than 30 days. SECTION 425 SPECIAL PROVISIONS FOR LICENSED 24-HOUR CARE FACILITIES IN
A GROUP I-1, R-3.1 or R-4 OCCUPANCY [SFM]
425.1 Scope. - The provisions of this section shall apply to 24-hour care facilities in a Group R-2.1, R-3.1, or R-4 occupancy licensed by a governmental agency.
425.2 General - The provisions in this section shall apply in addition to general requirements in this code.
425.2.1 - Restraint shall not be practiced in a Group R-2.1, R-3.1, or R-4 occupancies. Exception: Occupancies which meet all the requirements for a Group I-3 occupancy.
page10image24336
Residential Care Facilities Presentation Handout 10 June 1, 2011
425.2.2 - Pursuant to Health and Safety Code Section 13133, regulations of the State Fire Marshal pertaining to occupancies classified as Residential Facilities (RF) and Residential- Care Facilities for the Elderly (RCFE) shall apply uniformly throughout the state and no city, county, city and county, including a charter city or charter county, or fire protection district shall adopt or enforce any ordinance or local rule or regulation relating to fire and panic safety which is inconsistent with these regulations. A city, county, city and county, including a charter city or charter county may, pursuant to Health and Safety Code Section 13143.5, or a fire protection district may, pursuant to Health and Safety Code Section 13869.7, adopt standards more stringent than those adopted by the State Fire Marshal that are reasonably necessary to accommodate local climate, geological, or topographical conditions relating to roof coverings for Residential Care Facilities for the Elderly.
Exception: Local regulations relating to roof coverings in facilities licensed as a Residential Care Facility for the Elderly (RCFE) per Health and Safety Code Section 13133.
425.3 Building height and area provisions.
425.3.1
Group R-2.1, R-3.1 and R-4 shall be constructed in accordance with Table 503.
425.3.2 Limitations—six or less clients. Group R-3.1 occupancies where clients are housed above the first story, having more than two stories in height or having more than 3,000 square feet (279 m2) of floor area above the first story shall not be of less than 1- hour fire-resistance-rated construction throughout.
In Group R-3.1 occupancies housing a bedridden client, the client sleeping room shall not be located above or below the first story.
Exception: Clients who become bedridden as a result of a temporary illness as defined in Health and Safety Code Sections 1566.45, 1568.0832, and 1569.72. A temporary illness is an illness that persists for 14 days or less. A bedridden client may be retained in excess of the 14 days upon approval by the Department of Social Services and may continue to be housed on any story in a Group R 3.1 occupancy classified as a licensed residential facility.
Every licensee admitting or retaining a bedridden resident shall, within 48 hours of the resident’s admission or retention in the facility, notify the local fire authority with jurisdiction of the estimated length of time the resident will retain his or her bedridden status in the facility.
425.3.3 Limitations—seven or more clients. - Group R-4 occupancies where non- ambulatory clients are housed above the first story and there is more than 3,000 square feet (279 m2) of floor area above the first story or housing more than 16 clients above the first story shall be constructed of not less than 1-hour fire-resistance-rated construction throughout.
425.3.4 Non-ambulatory elderly clients.- Group R-4 occupancies housing non- ambulatory elderly clients shall be of not less than 1-hour fire-resistance-rated construction throughout.
425.4 Type of construction provisions.
Residential Care Facilities Presentation Handout 11 June 1, 2011
425.4.1- Group R-2.1 occupancies are not permitted in non-fire-resistance-rated construction; see Health and Safety Code Section 13131.5.
425.5 Fire-resistance-rated construction provisions.
425.5.1 Smoke barriers required.- Group R-2.1 and R-4 occupancies licensed as a Residential Care Facility (RCF) with individual floor areas over 6,000 square feet (557 m2) per floor, shall be provided with smoke barriers, constructed in accordance with Section 710.
Group R-2.1 occupancies housing bedridden clients shall be provided with smoke barriers constructed in accordance with Section 710 regardless of the number of clients.
When smoke barriers are required, the area within a smoke compartment shall not exceed 22,500 square feet (2090 m2) nor shall its travel distance exceed 200 feet (60 960 mm). Such smoke barriers shall divide the floor as equally as possible.
425.5.2 Smoke partitions.- In Group R-2.1 occupancies where smoke partitions are required, framing shall be covered with noncombustible materials having an approved thermal barrier with an index of not less than 15 in accordance with FM 4880, UL 1040, NFPA 286 or UL 1715.
425.5.3 Independent egress - At least two means of egress shall be provided from each smoke compartment created by smoke barriers. Means of egress may pass through adjacent compartments provided it does not return through the smoke compartment from which means of egress originated.
425.6.1 Interior wall and ceiling finish - Group R-3.1 occupancies housing a bedridden client shall comply with interior wall and ceiling finish requirements specified for Group I-2 occupancies in Table 803.9..
425.7 Fire protection system provisions.
425.7.1 Automatic sprinkler systems in Group R-2.1, R-3.1 and R-4 occupancies.
An automatic sprinkler system shall be installed where required in Section 903. 425.7.2 Fire alarm systems in Group R-2.1 and R-4 occupancies. -
An approved fire alarm system shall be installed where required in Section 907.
425.7.3 Smoke alarms in Groups R-2.1, R-3.1, and R-4 occupancies. - Smoke alarms
shall be installed where required in Section 907.2.11.1.
425.7.4 Hearing impaired. - See Section 907.5.2.3.
425.8 Means of egress provisions.
425.8.1 General. - In addition to the general means of egress requirements of Chapter 10, this section shall apply to Group R-2.1, R-3.1, and R-4 occupancies.
page12image20064 page12image20224 page12image20384 page12image20544 page12image20704
Residential Care Facilities Presentation Handout 12 June 1, 2011
425.8.2 Number of exits.
425.8.2.1 -
Group R-2.1, R-3.1, and R-4 occupancies shall have a minimum of two exits.
Exception: Ancillary use areas or occupancies shall have egress as required by Section 1021.
425.8.3 Egress arrangements.
425.8.3.1-
Egress through adjoining dwelling units shall not be permitted.
425.8.3.2 Group R-3.1 occupancies housing non-ambulatory clients. - In a Group R- 3.1 occupancy, bedrooms used by non-ambulatory clients shall have access to at least one of the required exits which shall conform to one of the following:
1. Egress through a hallway or area into a bedroom in the immediate area which has an exit directly to the exterior and the corridor/hallway is constructed consistent with the dwelling unit interior walls. The hallway shall be separated from common areas by a solid wood door not less than 13/8 inch (35 mm) in thickness, maintained self-closing or shall be automatic closing by actuation of a smoke detector installed in accordance with Section 715.4.8.
2. Egress through a hallway which has an exit directly to the exterior. The hallway shall be separated from the rest of the house by a wall constructed consistent with the dwelling unit interior walls and opening protected by a solid wood door not less than 13/8 inch (35 mm) in thickness, maintained self-closing or shall be automatic closing by actuation of a smoke detector installed in accordance with Section 715.4.8.
3. Direct exit from the bedroom to the exterior with a door not less than 3 feet in width and 6 feet 8 inches in height. Door shall be capable of opening at least 90 degrees and mounted so that the clear width of the exit way is not less than 32 inches.
4. Egress through an adjoining bedroom which exits to the exterior.
425.8.3.3 Group R-3.1 occupancies housing only one bedridden client. - In Group R- 3.1 occupancies housing a bedridden client and not provided with an approved automatic sprinkler system, all of the following shall apply:
1. In Group R-3.1 occupancies housing a bedridden client, a direct exit to the exterior of the residence shall be provided from the client sleeping room.
2. Doors to a bedridden client’s sleeping room shall be of a self-closing, positive latching 13/8 inch (35 mm) solid wood door. Such doors shall be provided with a gasket so installed as to provide a seal where the door meets the jam on both sides and across the top. Doors shall be maintained self-closing or shall be automatic closing by actuation of a smoke alarm in accordance with Section 715.4.8.
3. Group R-3.1 occupancies housing a bedridden client shall not have a night latch, dead
page13image23168 page13image23328
Residential Care Facilities Presentation Handout 13 June 1, 2011
bolt, security chain or any similar locking device installed on any interior door leading from a bedridden client’s sleeping room to any interior area such as a corridor, hallway and/or general use areas of the residence in accordance with Chapter 10.
4. The exterior exit door to a bedridden client's sleeping room shall be operable from both the interior and exterior of the residence.
5. Every required exit doorway from a bedridden client’s sleeping room shall be of a size as to permit the installation of a door not less than 3 feet (914 mm) in width and not less than 6 feet 8 inches (2032 mm) in height. When installed in exit doorways, exit doors shall be capable of opening at least 90 degrees and shall be so mounted that the clear width of the exit way is not less than 32 inches (813 mm).
Note: A sliding glass door can be used as an exterior exit doorway as long as it is operable from the inside and outside and the clear width of the exit way is not less than 32 inches (813 mm).
425.8.3.4 Intervening rooms. - A means of exit shall not pass through more than one intervening room. A means of egress shall not pass through kitchens, storerooms, closets, garages or spaces used for similar purposes.
Exception: Kitchens that do not form separate rooms by construction. 425.8.4 Corridors.
425.8.4.1 - Unless specified by Section 425.8.4, corridors serving Group R-2.1 and Group R-4 occupancies shall comply with Section 1018.1.
425.8.4.2 - The minimum clear width of a corridor shall be as follows:
1. Group R-2.1 occupancies shall have 60 inches (1524 mm) on floors housing non- ambulatory clients and 44 inches (1118 mm) on floors housing only ambulatory clients.
2. Group R-4 occupancies shall have 44 inches (1118 mm) on floors housing clients.
Exceptions:
  1. Corridors serving an occupant load of 10 or less shall not be less than 36 inches (914 mm) in width.
  2. Corridors serving ambulatory persons only and having an occupant load of 49 or less shall not be less than 36 inches (914 mm) in width.
In Group R-2.1 occupancies provided with fire sprinklers throughout and which are required to have rated corridors, door closers need not be installed on doors to client sleeping rooms.
3. Group R-3.1 occupancies shall have 36 inches (914 mm) on floors housing clients.
page14image21496
Residential Care Facilities Presentation Handout 14 June 1, 2011
425.8.4.3 - In Group R-2.1 and Group R-4 occupancies having smoke barriers, cross- corridor doors in corridors 6 feet (1829 mm) or less in width shall have, as a minimum, a door 36 inches (914 mm) in width.
425.8.5 Changes in level.- In Group R-3.1 occupancies housing non-ambulatory clients, changes in level up to 0.25 inch (6 mm) may be vertical and without edge treatment. Changes in level between 0.25 inch (6 mm) and 0.5 inch (12.7 mm) shall be beveled with a slope no greater than 1 unit vertical in 2 units horizontal (50 percent slope). Changes in level greater than 0.5 inch (12.7 mm) shall be accomplished by means of a ramp.
425.8.6 Stairways.
425.8.6.1 - Group R-2.1 occupancies housing more than six non-ambulatory clients above the first floor shall be provided with two vertical exit enclosures. Stairway enclosures shall be in compliance with Section 1020. Exceptions to Section 1020 shall not apply in facilities licensed as a 24-hour care facility.
425.8.6.2 - Group R-3.1 occupancies may continue to use existing stairways (except for winding and spiral stairways which are not permitted as a required means of egress) provided the stairs have a maximum rise of 8 inches (203 mm) with a minimum run of 9 inches (229 mm). The minimum stairway width may be 30 inches (762 mm).
425.8.7 Floor separation. - Group R-3.1 occupancies shall be provided with a non-fire resistance constructed floor separation at stairs which will prevent smoke migration between floors. Such floor separation shall have equivalent construction of 0.5 inch (12.7 mm) gypsum wallboard on one side of wall framing.
Exceptions:
  1. Occupancies with at least one exterior exit from floors occupied by clients.
  2. Occupancies provided with automatic fire sprinkler systems complying with Chapter
    9.
425.8.7.1 Doors within floor separations. - Doors within such floor separations shall be tight fitting solid wood at least 13/8 inches (35 mm) in thickness. Door glazing shall not exceed 1,296 inches (32 918 mm) with no dimension greater than 54 inches (1372 mm). Such doors shall be positive latching, smoke gasketed and shall be automatic-closing by smoke detection.
425.8.8 Fences and gates. - Grounds of a residential care for the elderly facility serving Alzheimer’s clients may be fenced and gates therein equipped with locks, provided safe dispersal areas are located not less than 50 feet (15 240 mm) from the buildings. Dispersal areas shall be sized to provide an area of not less than 3 square feet (0.282) per occupant. Gates shall not be installed across corridors or passageways leading to such dispersal areas unless they comply with egress requirements.
425.8.9 Basement exits. - One exit is required to grade level when the basement is accessible to clients.
page15image24088 page15image24248 page15image24408 page15image24568
Residential Care Facilities Presentation Handout 15 June 1, 2011
425.8.10 Delayed egress locks. - See CBC 1008.1.8.6.
425.9 Request for alternate means of protection for facilities housing bedridden clients.- Request for alternate means of protection shall apply to Sections 425 through 425.9. Request for approval to use an alternative material, assembly or materials, equipment, method of construction, method of installation of equipment or means of protection shall be made in writing to the local fire authority having jurisdiction by the facility, client or the client’s authorized representative. Sufficient evidence shall be submitted to substantiate the need for an alternate means of protection.
The facility, client or the client’s representative or the local fire authority having jurisdiction may request a written opinion from the State Fire Marshal concerning the interpretation of the regulations promulgated by the State Fire Marshal for a particular factual dispute. The State Fire Marshal shall issue the written opinion within 45 days following the request.
Approval of a request for use of an alternative material, assembly or materials, equipment, method of construction, method of installation of equipment, or means of protection made pursuant to this section shall be limited to Group R-3.1 occupancies housing a bedridden client.
Approvals made by the local fire authority having jurisdiction and the written opinion by the State Fire Marshal shall be applicable only to the requesting facility and shall not be construed as establishing any precedent for any future request by that facility or any other facility.
425.10 Temporarily bedridden clients. - Clients who become temporarily bedridden as defined in Health and Safety Code Section 1569.72, as enforced by the Department of Social Services, may continue to be housed on any story in Group R-2.1, R-3.1, or R-4 occupancies classified as Residential Care Facilities for the Elderly (RCFE). Every Residential Care Facility for the Elderly (RCFE) admitting or retaining a bedridden resident shall, within 48 hours of the resident's admission or retention in the facility, notify the local fire authority with jurisdiction of the estimated length of time the resident will retain his or her bedridden status in the facility.
TABLE 503 ALLOWABLE HEIGHT AND BUILDING AREASa
Height limitations shown in feet above grade plane. Story limitations shown as stories above grade plane. Building area limitations shown in square feet, as determined by the definition of “Area, building,” per story

page16image63232 page16image63392 page16image63552 page16image63712 page16image64352
page16image65264 page16image65424 page16image65584 page16image65744 page16image65904 page16image66064 page16image66224 page16image66384 page16image66544 page16image66704 page16image66864 page16image67024 page16image67184 page16image67344 page16image67504 page16image67664 page16image67984 page16image78488 page16image78648 page16image78808 page16image78968 page16image79128 page16image79288 page16image79448 page16image79608 page16image79768 page16image79928

  1. Section 504.2, Allowable height increase due to automatic sprinkler system installation.
  2. Section 506.2, Allowable area increase due to street frontage.
  3. Section 506.3, Allowable area increase due to automatic sprinkler system installation.
  4. Section 507, Unlimited area buildings.
For open parking structures, see Section 406.3.
For private garages, see Section 406.1.
See Section 415.5 for limitations.
[SFM] See Section 408.1.1 for specific exceptions for one-story Type IIA, IIIA or VA construction.

Restraint shall not be permitted in any building except in Group I-3 occupancies constructed for such use (See Section 408.1.2)
Nonambulatory persons shall be limited to the first two stories.
Nonambulatory persons shall be limited to the first five stories.
Nonambulatory elderly clients are not permitted to buildings of these types of construction. See sections 425.3.3 and 425.3.4.

A UL 55,000 19,000 NP 16,500 NP NP 10,500 NP
R-3/R- 3.1
S A
page17image21328 page17image21488 page17image22080 page17image22240 page17image22400 page17image22992
UL UL
page17image25528 page17image25952 page17image26112 page17image26536
11 UL
page17image28272 page17image28696 page17image28856 page17image29280
4 UL
page17image31016 page17image31440 page17image31600 page17image32024
4 UL
page17image33760 page17image34184 page17image34344 page17image34768
4 UL
4 UL
page17image37600 page17image37760 page17image38352 page17image38512 page17image38672 page17image39264
4 UL
3 UL
page17image42864 page17image43024 page17image43616 page17image43776
3 UL
R-4
S A
page17image51584 page17image51744 page17image52336 page17image52496 page17image52656 page17image53248
UL UL
page17image55600 page17image55760 page17image56352
page17image56712 page17image57136 page17image57296 page17image57720
11h UL
page17image59272 page17image59696
page17image60056 page17image60480 page17image60640 page17image61064
4g 24,000
page17image62616 page17image63040
page17image63400 page17image63824 page17image63984 page17image64408
4i 16,000
page17image65960 page17image66384
page17image66744 page17image67168 page17image67328 page17image67752
4g 24,000
page17image69304 page17image69728
4i 16,000
page17image71360 page17image71520 page17image72112 page17image72272 page17image72432 page17image73024
4i 20,500
page17image75376 page17image75536 page17image76128
3g 12,000
page17image77720 page17image77880 page17image78472 page17image78632
2i 7,000
page17image81096 page17image81256
For SI: 1 foot = 304.8 mm, 1 square foot = 0.0929m2. UL = Unlimited, NP = Not permitted.
page17image83120 page17image83280
903.2.8 Group R. [F]
An automatic sprinkler system installed in accordance with Section 903.3 shall be provided throughout all buildings with a Group R fire area.
Exceptions:
1. Existing Group R-3 occupancies converted to Group R-3.1 occupancies not housing bedridden clients, not housing nonambulatory clients above the first floor and not housing clients above the second floor.
2. Existing Group R-3 occupancies converted to Group R-3.1 occupancies housing only one bedridden client and complying with section 425.8.3.3.
3. Pursuant to Health and Safety Code Section 13113, occupancies housing ambulatory children only, none of whom are mentally ill or mentally retarded, and the buildings or portions thereof in which such children are housed are not more than two stories in height, and buildings or portions thereof housing such children have an automatic fire alarm system activated by approved smoke detectors.
4. Pursuant to Health and Safety Code Section 13143.6, occupancies licensed for protective social care which house ambulatory clients only, none of whom is a child (under the age of 18 years), or who is elderly (65 years of age or over).
When not used in accordance with Section 504.2 or 506.3, an automatic sprinkler system
Residential Care Facilities Presentation Handout 17 June 1, 2011
installed in accordance with Section 903.3.1.2 shall be allowed in Group R-2.1 occupancies.
An automatic sprinkler system designed in accordance with Section 903.3.1.3 shall not be utilized in Group R-2.1 or R-4 occupancies
SECTION 906 PORTABLE FIRE EXTINGUISHERS
906.1 General. [F] -
Portable fire extinguishers shall be installed in the following locations:
1. InnewandexistingGroupR-2.1,R-3.1andR-4occupancies.
2. Within30feetofcommercialcookingequipment.
3. Inareaswhereflammableorcombustibleliquidsarestoredorused.
4. WhererequiredbytheCaliforniaFireCodesectionsindicatedinTable906.1. 5. WhererequiredbytheCaliforniaCodeofRegulations,Title19,Division1.

SECTION 907 FIRE PROTECTION SYSTEMS
907.2.9.3 Licensed group R-2.1 occupancies. [F] - Licensed Group R2.1 occupancies housing more than six non-ambulatory, elderly clients shall be provided with an approved manual and automatic fire alarm system.
Exceptions: Buildings housing non-ambulatory clients on the first story only and which are protected throughout by the following:
1. An approved and supervised automatic sprinkler system, as specified in Sections 903.3.1.1 or 903.3.1.2, which upon activation will initiate the fire alarm system to notify all occupants.
  1. A manual fire alarm system.
  2. Smoke alarms required by Section 907.2.11.
907.2.10 Group R-4. [F] - Fire alarm systems and smoke alarms shall be installed in Group R-4 occupancies as required in Sections 907.2.10.1 through 907.2.10.3.
907.2.10.1 Fire alarm system for Group R-4 occupancies. [F] - An approved manual and automatic fire alarm system shall be installed in Group R-4 occupancies.
Exceptions:
1. Protective social care occupancies housing persons none of whom are physically or mentally handicapped or non-ambulatory and which provide supervisory services such as alcoholism or drug abuse recovery or treatment facilities, halfway houses operated by the California Department of Corrections, and similar facilities and are provided with a manual fire alarm box which will actuate a distinctive fire alarm signal that can be heard throughout the facility.
2. Protective social care facilities provided with an automatic sprinkler system which complies with Chapter 9 and are provided with a manual fire alarm box which will actuate a distinctive fire alarm signal that can be heard throughout the facility.
Residential Care Facilities Presentation Handout 18 June 1, 2011
907.2.10 Single- and multiple-station smoke alarms. [F] - Listed single- and multiple- station smoke alarms complying with UL 217 shall be installed in accordance with the provisions of this code and the household fire-warning equipment provisions of NFPA 72.
Exception: For Group R occupancies. A fire alarm system with smoke detectors located in accordance with this section may be installed in lieu of smoke alarms. Upon actuation of the detector, only those notification appliances in the dwelling unit or guest room where the detector is actuated shall activate.
907.2.10.1 Where required. [F] - Single- or multiple-station smoke alarms shall be installed in the locations described in Sections 907.2.10.1.1 through 907.2.10.1.3.
907.2.10.1.1 Group R-1. [F] - Single- or multiple-station smoke alarms shall be installed in all of the following locations in Group R-1:
  1. In sleeping areas.
  2. In every room in the path of the means of egress from the sleeping area to the door
    leading from the sleeping unit.
  3. In each story within the sleeping unit, including basements. For sleeping units with split
    levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
  4. In enclosed common stairwells of multiple-dwelling complexes.
907.2.11.2 Groups R-2, R-3, R-3.1, R-4 and R2.1. [F] Smoke Alarms - Single- or multiple-station smoke alarms shall be installed and maintained in Groups R-2, R-3, R-3.1, R-4 and R2.1, regardless of occupant load at all of the following locations:
1. On the ceiling or wall outside of each separate sleeping area in the immediate vicinity of bedrooms.

  1. In each room used for sleeping purposes.
  2. In each story within a dwelling unit, including basements but not including crawl spaces
and uninhabitable attics. In dwellings or dwelling units with split levels and without an intervening door between the adjacent levels, a smoke alarm installed on the upper level shall suffice for the adjacent lower level provided that the lower level is less than one full story below the upper level.
4. In enclosed common stairwells of apartment complexes and other multiple-dwelling complexes.
5. In a Group R-3.1 occupancy, in addition to the above, smoke alarms shall be provided throughout the habitable areas of the dwelling unit except kitchens.

907.2.9.3 Group R2.1. [F] - Single- or multiple-station smoke alarms shall be installed and maintained in sleeping areas in Group occupancies.
Exception: Single- or multiple-station smoke alarms shall not be required where the building is equipped throughout with an automatic fire detection system in accordance with Section 907.2.6.
907.2.10.1.4 Group I-4 occupancies. - Large-family day-care homes shall be equipped with State Fire Marshal approved and listed single-station residential-type smoke alarms.
Residential Care Facilities Presentation Handout 19 June 1, 2011
907.2.10.1.5 Group R-3.1. - In all facilities housing a bedridden client, smoke alarms shall receive their primary power from the building wiring when such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms shall be electrically interconnected so as to cause all smoke alarms to sound a distinctive alarm signal upon actuation of any single smoke alarm. Such alarm signal shall be audible throughout the facility at a minimal level of 15 db above ambient noise level. These devices need not be interconnected to any other fire alarm device, have a control panel, or be electrically supervised or provided with emergency power.
907.2.10.2 Power source. - In new construction and in newly classified Group R-3.1 occupancies, required smoke alarms shall receive their primary power from the building wiring where such wiring is served from a commercial source and shall be equipped with a battery backup. Smoke alarms shall emit a signal when the batteries are low. Wiring shall be permanent and without a disconnecting switch other than as required for over-current protection.
Exception: Smoke alarms are not required to be equipped with battery backup in Group R- 1 where they are connected to an emergency electrical system.
907.2.10.3 Interconnection. [F] - Where more than one smoke alarm is required to be installed within an individual dwelling unit in Group R-2, R-3, R-3.1, or R-4, or within an individual dwelling unit or sleeping unit in Group R-1, the smoke alarms shall be interconnected in such a manner that the activation of one alarm will activate all of the alarms in the individual unit. The alarm shall be clearly audible in all bedrooms over background noise levels with all intervening doors closed.
907.2.10.4 Acceptance testing. [F] - When the installation of the alarm devices is complete, each detector and interconnecting wiring for multiple-station alarm devices shall be tested in accordance with the household fire warning equipment provisions of NFPA 72.
Residential Care Facilities Presentation Handout 20 June 1, 2011
State Fire Marshal Interpretations Care Facilities
Date Issued 04-21-2000
Interpretation 00-003
Topic: Exiting from R, Division 2 Occupancies housing non-ambulatory clients.
Code Section(s): 1007.6.3.2.2, California Building Code (1998)
Requested by: Mary Miller, Fire Marshal, Modesto Fire Department, 1010 Tenth Street, Modesto, CA 95353

1. Can a person exit through two intervening rooms in a Group R, Division 2 Occupancy housing six or less non-ambulatory clients?
One of the two required exits can be through a hallway and then to another bedroom that has an exit directly to the outside. Furthermore, the code also allows the exit to be through an adjacent room (such as a bathroom) and then through a bedroom with direct exit to the outside.
2. Is it the intent of the code to allow both of the required exits to be through intervening rooms?
No. the preferred means of exiting from the bedrooms housing non-ambulatory clients should be directly to the exterior. However, when this is not practical, the exiting may be through an intervening room.
3. Is the hallway considered an intervening room?
The hallway would not be considered an intervening room in this specific case.
4. Can section 1004.2.2 be ignored because section 1007.6.3.2.2 is more specific? Section 1007.6.3.2.2 is the only section applicable for this issue.
5. Can we apply these requirements to ambulatory facilities?
No. In ambulatory facilities housing six or fewer clients, exiting is required as per a Group R Division 3 Occupancy.
6. Is there a provision for door width for a non-ambulatory client in a wheel chair so they can move freely about a care home?
It appears that everything we find references occupant loads of 10 or more. The code appears to be silent in this regard as it speaks to door widths of rooms housing 10 or more. The intent of the code is to allow the clients to move about freely. Consequently, the doors from the rooms housing non-ambulatory clients must be adequate to accommodate the width of the wheelchair. Since there is no standard size of wheelchair, the door width will have to depend on the particular client housed in the room.
7. Is there a provision for door width for ambulatory clients?
There is not specific code reference for this issue. The requirements would be those that are applicable to a Group R, Division 3 Occupancy.
Date Issued 08-07-00 Interpretation 00-011
Topic: Group R, Division 2 Accessibility
Code Section(s) §13146, Health and Safety Code, Chapter 11, California Building Code (1998 ed.)
Requested by Paul Olkowski, San Mateo City Fire Department, 1941 O’Farrell St. #102, San Mateo, CA 94403-1388
1. Is it the responsibility of the local fire authority to enforce all regulations
for Group R, Division 2 Occupancies, including plan review for new facilities?
The California Health and Safety Code, Section 13146, requires that the local fire authority enforce fire and panic regulations in various occupancies. This includes
Residential Care Facilities Presentation Handout 21 June 1, 2011
plan review for compliance with SFM regulations. However, we would encourage the fire authority to work closely with the local building officials so that a comprehensive review of all applicable standards is rendered — including locally adopted ordinances.
2. Is a Group R, Division 2 facility housing non-ambulatory clients required to comply with the requirements of Chapter 11 concerning Accessibility (e.g., fire alarm strobe lights, exterior ramps, 36-inch hallways and doors, leverstyle door hardware, etc.).
The State Fire Marshal only adopted certain sections of Chapter 11B of the California Building Code in its entirety. Since Chapter 11B is specific to public buildings, those sections adopted by the SFM are not applicable to R-2 Occupancies. Therefore, the accessibility standards applicable to Group R, Division 2 facilities are those adopted at the local level for residential applications as found in Chapters 11 and 11A.
3. When a single-family dwelling applies for a permit to convert the occupancy to a non-ambulatory community care home, is it the intent of the State Building Code to provide the non- ambulatory residents the same accessibility options as for any other occupant?
Please refer to the answer to the prior question as it applies to this question.
Date Issued 11-20-00 Interpretation # 00-017
Topic Fire Drills in Group R, Division 2 Occupancies
Code Section(s) §3.10, Title 19, California Code of Regulations
Requested by: Gregory Lake, Sacramento Metropolitan Fire District, 2101 Hurley Way Sacramento, CA 95825-3208
Are fire drills required by State regulation in a Group R, Division 2.2.1 Occupancy?
No. There are no requirements for monthly fire drills for a Group R, Division 2 Occupancy. Section 3.10 of Title 19 speaks only to the evacuation and relocation of occupants. When this code section addresses “fire drills”, it specifically is directed at those occupancies that do require fire drills (e.g., schools). In addition, State Law provides that requirements for Group R, Division 2 Occupancies housing six or less cannot be amended by local ordinance.
Date Issued 11-20-00 Interpretation # 00-019
Topic Accessibility Standards in Group R, Division 2 Occupancies
Code Section(s): Chapters 10 and 11, California Building Code (1998 ed) Requested by: Gregory Lake, Sacramento Metropolitan Fire District
2101 Hurley Way, Sacramento, CA 95825-3208
In a Group R, Division 3 dwelling, is it the intent of the Code to require the following before it may house a Group R, Division 2.2.1 Occupancy:
1. Interior “changes in level” ramps with handrails per CBC for access to common areas not in exit path;
2. 32-inch wide doors to the bathroom, commode room, and other common use areas not in the exit path from the sleeping areas as noted in Section 1007;
3. Consideration of every common-area door as a required exit door from that room;
4. Lever hardware on the doors and gates.

Residential Care Facilities Presentation Handout 22 June 1, 2011
No. Common areas are specific to Chapter 11 only and not intended to be inter-changeable with other sections of the Code.
Date Issued 06-17-02 Interpretation 02-014
Topic: Location of Property R-6 Occupancies
Code Section(s) §317A, California Building Code (1998)
Requested by Robert Bohman, Deputy Fire Marshal, Alameda County Fire Department 2241 Redwood Road, Castro Valley, CA 94546
Is it the intent of CBC Section 317A to allow setback from the property line of only three feet for a Group R, Division 6.2 occupancy if the building is designed with a non-rated exterior wall and unprotected openings even when the occupancy load is greater than ten?
No. Section 316A states that a Group R, Division 6.2 occupancy shall not exceed the type of construction as specified for occupancies classified Group R Division 1 occupancy.
Date Issued 06-17-02 Interpretation 02-025
Topic: Changes in Level in Corridors and Hallways R-2 Occupancies
Code Section(s): §1007.6.3.4, California Building Code (1998)
Requested by: Bryan Wadlington, San Miguel Fire Protection District, 2850 Via Orange Way Spring Valley, CA 91978-5331
Since all required exits in Group R, Division 2 occupancies must go to a public way, is it the intent of the State Fire Marshal that Section 1007.6.3.4 of the California Building Code (1998) be used for the entire path of travel to the public way or is this section only intended to apply to the interior hallways and corridors?
Section 1007.6.3.4 applies specifically to the interior exiting system.
Date Issued 12-05-02 Interpretation 02-039
Topic: Changes in Elevations for Group R, Division 2 Occupancies
Code Section(s): Section 1007.6.3.4, California Building Code (1998 ed)
Requested by: Steve Holtrust: Ontario Fire Department, 415 East “B” Street, Ontario, CA 91764
Does Section 1007.6.3.4 apply to all Group R, Division 2 occupancies or only those that have non-ambulatory clients?
No. This section would only apply for non-ambulatory clients as defined in Section 215, California Building Code.
Date Issued 12-05-02 Interpretation 02-046
Topic: Exiting from Group R-2.2.1 with Non-Ambulatory Clients
Code Section(s): Section 1007.6.3.2.1, California Building Code (1998 ed)
Requested by: Colleen Balch, Carlsbad Fire Department, 1635 Faraday Avenue
Carlsbad, CA 92008
1. Does Section 1007.6.3.2.1 apply to Group R, Division 2.2.1 occupancies that house non-ambulatory clients?
Yes. Section 1007.6.3.2.1 applies to the bedrooms used by non-ambulatory clients in Group R, Division 2.2.1 occupancies built of non-rated construction.
2. How do you apply section 1007.6.3.2.4? It appears that the clients are exiting through more than one intervening room if they exit through the hallway.
For purposes of determining the number of intervening rooms, the room that the clients exit from is not counted and the hallway is not considered a room for purposes of exiting in this
Residential Care Facilities Presentation Handout 23 June 1, 2011
type of occupancies. Clients may exit from a bedroom to the hallway and through another bedroom that has a direct exit to the exterior. They may not exit from the hallway into a common living area such as an entryway or living room.
Date Issued 12-05-02 Interpretation 02-050
Topic: Door Width in Group R, Division 2 Occupancies
Code Section(s): Section 1003.3.1.3, California Building Code (1998 ed)
Requested by: Ralph Crane, Fire Marshal, Rancho Cucamonga Fire Protection District P.O. Box 807, Rancho Cucamonga,CA.91729-0807
Is it the intent of Section 1003.3.1.3 to require that the net unobstructed door width, WITH NO EXCEPTIONS, be no less than 32” through bedroom doors on an existing Group R, Division 3 occupancy being converted for use as a Group R, Division 2.2.1 facility?
No. Section 1003.3.1.3 is specific to occupancies serving 10 or more clients. An existing Group R, Division 3 being converted to a Group R, Division 2.2.1 does not fall into this criteria and can have exit doors with a clear exit width of 28 inches as the clients will all
be ambulatory.

Date Issued 12-05-02 Interpretation 02-056
Topic: R-2 Occupancies
Code Section(s): Section 506 (#6), California Building Code (1998 ed)
Requested by: Pedro Garcia/Steve Kuchenski, 310 North Lake Avenue #920, Pasadena, CA 91101-4129
Does Provision #6 in Section 506 refer to Section 904.2.9 or does it refer to Group R, Division 2 occupancies referenced in Section 904.2.10?
Provision #6 refers to Group R, Division 2 occupancies. Provision #6 is a misprint and should refer to Section 904.2.10 as this section is where the sprinkler requirements for Group R, Division 2 occupancies reside.
Date Issued 12-05-02 Interpretation 02-057
Topic: Exiting in RCFE’s
Code Section(s): §1007.6, California Building Code (1998 ed)
Requested by: Aleyda and Jeffrey Hanson, Elder Eden, 1226 Bella Oaks Lane
Napa, CA 94558
Are Residential Care Facilities for the Elderly (RCFE) which have six or fewer residents limited to direct exiting from each resident sleeping room?
No. RCFEs that house six or fewer ambulatory residents may have the type of exiting allowed for Group R, Division 3 occupancies (single family dwellings.) RCFE’s that house six or fewer non-ambulatory residents may have any of the following types of exiting from each sleeping room:
a. Direct exit to exterior from bedroom.
b. Egress through an adjoining bedroom that has a direct exit to exterior.
c. Egress through hallway/corridor that has an exterior exit
d. Egress through a hallway/corridor or area and into a bedroom that has a
direct exit to exterior.

Date Issued 12-05-02 Interpretation 02-058
Topic: Group R, Division 2.1.1 Facilities
Code Section(s): Sections 310.9 & 310.10.2, California Building Code (1998 ed)
Residential Care Facilities Presentation Handout 24 June 1, 2011
Requested by: Stephen Hart, NASIP, 1050 Eileen Way, Sacramento, CA 95831-5812
1. Is an existing (April 1991) Residential Care Facility (R-2.1.1) that has had no change to either their license or to the building structure required to have smoke detectors in the bedrooms?
No. There were no smoke detector requirements in sleeping rooms at the time this facility was licensed.
2. Is at least one manual pull station also required?
No. There were no pull station requirements for facilities housing six or less at the time this facility was licensed.
Date Issued 02-10-03 Interpretation 03-002
Topic: Area of Rescue Assistance
Code Section(s): §1114B.2.1, California Building Code (1998 ed)
Requested by: Sid Akhzar, 5567 Reseda Blvd #209, Tarzana, CA 91358
Both Section 1114B of the 1998 California Building Code and ADAAG 4.1.3(g) agree that a “supervised automatic sprinkler system” overrides the requirement for Area of Rescue Assistance. Does the State Fire Marshal agree that any occupancy can dispense with rescue assistance by installing a supervised automatic sprinkler system?
Yes. Exception #1 of Section 1114B.2.1 states that areas of evacuation assistance are not required in buildings or facilities having a supervised automatic sprinkler system.
Date Issued 02-10-03 Interpretation 03-005
Topic: Residential Care Occupancies.
Code Section(s): §310.1, California Building Code (2001 ed)
Requested by: Michelle Douglas, Colton Fire Department, 303 “E” St, Colton, CA 92324
Is a small family home having a licensed capacity of four infants as defined in Section 310 classified as a Group R, Division 2.2 occupancy?
No. The total capacity of the facility you describe is less than six clients. Since infants
can not be defined as non-ambulatory due to age per Section 210, the facility more closely resembles a Group R, Division 2.2.1 occupancy.

Date Issued: 03-25-04 REVISED Interpretation 03-018
Topic: Group R, Divisions 2.1.1 and 2.2.1
Code Section(s): §1267.8,13143,13195,13113.7(2) and 1275 California Health and Safety Code
Requested by: K Chin, Altos Care, Inc.2492 Aram Ave. San Jose, CA 95128
1. Considering the provisions of Section 1267.8(a) of the California Health and Safety Code, are commercial or residential standards for fire and life safety, egress and accessibility applicable to Group R, Division 2.1.1 occupancies when the code is interpreted by local plan checkers and fire inspectors?
Only those regulations that have been adopted by the State Fire Marshal shall apply to fire and life safety, egress and accessibility.
2. Should local fire inspectors or planners cite commercial or residential standards when inspecting a Group R, Division 2.1.1 occupancy?
No. Commercial standards do not apply to Group R, Division 2 occupancies. The Health and Safety Code requires that these facilities model as closely as possible to a Group R, Division 3 Occupancy.
Residential Care Facilities Presentation Handout 25 June 1, 2011
3. Considering the provisions of Section 1267.8 of the Health and Safety Code, what are the closest occupancy standards for life safety, egress and accessibility that “special occupancy” fire department planners and inspectors should be using when inspecting a Group R, Division 2.1.1 occupancy (i,e. can local fire departments apply commercial standards)?
Fire inspectors and plan checkers shall only apply local ordinances for restrictions on building heights, setbacks, lot dimensions, or placement of signs as long as such restrictions are identical to those applied to other single-family residences.
4. Considering Section 13143 of the Health and Safety Code, in Group R, Division 2.2.1 occupancies, are illuminated exit signs required above all exit doors and in hallways to indicate the exit path of egress ( including illuminated exit signs in all client bedrooms that have a direct exit to the exterior and illuminated hallway exit signs indicating which bedrooms have direct exits to the exterior)?
No. Exit signs indicating which bedrooms have direct exits to the exterior are not required in this type of occupancy.
5. Considering Section 13143.8 of the Health and Safety Code, can the local fire department require stricter “commercial” fire and life safety standards for egress, life safety and accessibility in Group R, Division 2.1.1 occupancies than required by the SFM?
No.
6. Considering Section 13195 of the Health and Safety Code, in Group R, Division 2.2.1 occupancies (ambulatory) are fire sprinklers and a monitored fire sprinkler system that conform to NFPA #13-D required? If required, does the monitored sprinkler system need two dedicated telephone lines for monitoring? Does the monitored system require quarterly inspections by the alarm company (equivalent to a commercial system)?
No. There are no requirements in the Health and Safety Code or in the California
Building Code requiring a sprinkler system in Group R, Division 2.2.1
occupancies that house six or fewer clients.
7. Considering Section 13113.7 (2) of the Health and Safety Code, can the local building or fire departments require in-room smoke detectors in all rooms in Group R, Division 2.1.1 facilities that already have monitored fire alarms with a NFPA-13D fire sprinkler system? Has this requirement been waived by the State Fire Marshal? No. Local ordinances are not applicable to Group R, Division 2.1.1 occupancies. Only those regulations adopted by the State Fire Marshal are applicable. The requirements of Section 13113.7 (2), Health and Safety Code have not been waived and they are provided for in the smoke alarms required by Section 310.9.1.1 of the California Building Code (2001 ed)
8. Considering Section 19956 of the Health and Safety Code, are handrails required on ADA compliant walkways sloped 1:20 or greater? Can handrails be required by the Department of Health Services for licensing purposes? Are handrails required on landings that are less than 30 inches above grade?
The State Fire Marshal does not regulate the application of American with Disabilities Act.
9. Considering Section 1275 of the Health and Safety Code, can the Department of Health Services amend or apply stricter (e.g. commercial) fire standards for egress and life safety for Group R, Division 2.1.1 than what is specified by the State Fire Marshal (including accessibility/ramp requirements, etc.)?
No.
Residential Care Facilities Presentation Handout 26 June 1, 2011
Date Issued 03-18-03 Interpretation 03-019
Topic: Exiting from R-2.2.1
Code Section(s) §1007.6.3.2.2, California Building Code (2001 ed)
Requested by: John Gifford, John Gifford Construction, PO Box 2470, Porterville, CA 93258
1. In Group R, Division 2.2.1 occupancy housed in a one-story single-family residence where the entry door is the primary exit, is it the intent of §1007.6.3.2.2 to require direct or semi-direct exit from each client bedroom or does this just apply to those bedrooms which contain non-ambulatory clients?
No. The exiting requirements of §1007.6.3.2.2 apply to the bedrooms of Group R,
Division 2.2.1 occupancies used by non-ambulatory clients only. It is not the
intent of this section to apply these requirements to ambulatory clients.
2. If all of the clients in a single-story Group R, Division 2.2.1 occupancy are ambulatory, wouldn’t the window escape method specified in §310.4 provide the second required exit?
No. All Group R, Division 2 occupancies must have at least two exits. The second required exit cannot be a window. It must be an exit door.
Date Issued 10-21-03 Interpretation 03-025
Topic: Group R, Division 2.2.1 and Group R, Division 2.1.1 Occupancies
Code Section(s): §1007.6.3.1.1, California Building Code (2001 ed)
Requested by: Mike Bell, Rancho Cucamonga Fire Department, 10500 Civic Center Drive, Rancho Cucamonga, CA 91730
Does §1007.6.3.1.1 apply to existing single-family units (Group R, Division 3 occupancies) that convert to a Group R, Division 2.1.1 or Division R2.2.1? If so, must the exits be the existing front and back door or can the occupant install a new exit(s) that meet the code and leave the existing doors as is?
Yes. For a Group R, Division 2.2.1, the exits can be the front and back door as long as they meet the requirements of §1007.6.3.2.3 which states, “A means of exit shall not pass through kitchens, storerooms, closets or spaces used for similar purposes.” For a Group R, Division 2.1.1, additional exits may have to be provided to comply with the direct or semi- direct requirements of §1007.6.3.2.2 for non-ambulatory clients.
Date Issued 10-21-03 Interpretation 03-028
Topic: Fire Alarm Devices and Dead Bolts in Group R, Division 3
Code Section(s): §310.15.4 and §1003.3.1.8, California Building Code
Requested by: Mark Braley, Riverside County Fire Department, 210 W. San Jacinto Ave., Paris, CA 92570
1. Must fire alarm devices referenced in §310.15.4 be State Fire Marshal approved and listed?
No. §310.15.4 requires only a device suitable for sounding a fire alarm --- not a listed fire alarm device. Therefore, any device approved by the Authority Having
Jurisdiction (e.g., bell, whistles, air-horn, etc.) may be used. However, when the device installed is a fire alarm pull station that would normally be part of a fire alarm system, then these components must be SFM approved and listed.
2. Does the operation of a dead bolt used in addition to the locking door hardware require special knowledge or effort? Must the door hardware and dead bolt be interconnected so that they release with single action?
No. In individual dwelling units of Group R, Division 3 occupancies are permitted
Residential Care Facilities Presentation Handout 27 June 1, 2011
to secure the entry door with a night latch, dead bolt or security chain.
Date Issued 10-21-03 Interpretation 03-034
Topic: Group R, Division 2 Occupancies Located Above the First Floor
Code Section(s): §3.23, Title 19, California Code of Regulations
Requested by: Walt McDermott, 1003 Via Mil Cumbres, Solana Beach, CA 92075
In Group R, Division 2 and Group R, Division 6 occupancies that house non- ambulatory persons above the first floor, must the buildings be of Type I- FR or Type II- FR construction as specified in §3.23?
No. The issue of non-ambulatory persons above the first story is addressed in law [§13131.5 (b), California Health and Safety Code] for facilities housing more than six elderly clients. §310.2.2 of the California Building Code addresses other Group R, Division 2 occupancies, while Exception #1 in Appendix Chapter A, Section 316A.1 addresses Group R, Division 6 facilities housing non-ambulatory clients above the first floor. (Note: §3.23 is being revised.)
Date Issued: 02-05-04 Interpretation 04-004
Topic: Construction Limits for Group R, Division 2.1 Occupancies
Code Section(s): §13131.5, California Health and Safety Code
Requested by: Kerwin Lee, Rolf Jensen and Associates, 2125 Oak Grove Rd #300 Walnut Creek, CA 94598
Can a residential care occupancy (Group R, Division 2.1) having six or fewer non- ambulatory residents/clients be housed on the third floor of a Type V-1 hour building? The first two floors of the building house more than six non-ambulatory residents/clients.
No. Health and Safety Code Section 13131.5(b) limits the housing of non-ambulatory persons in a Type V-1 hour building only to the first and second floor. Further, you will find that Table 5-B of the California Building Code (2001 ed) limits a Group R, Division 2.1 occupancy housed in a Type V-1 hour building to two stories as well. When housing non- ambulatory persons on the third, fourth or fifth floor, Section 13131.5(c)(3) of the California Health and Safety Code requires that the entire building be of Type II Fire Resistive construction. It is not the intent of the code to divide or separate the occupants in a Group R, Division 2.1 occupancy to circumvent minimum requirements.
Date Issued: 07-30-04 Interpretation 04-012
Topic: Cooking Appliances in R-2.1 and R-2.2 Occupancies
Code Section(s): §310.2.2, California Building Code (2001)
Requested by: Karen Vaudreuil, Fire Marshal, Carlsbad Fire Department, 1635 Faraday Ave., Carlsbad, CA. 92008
A business is requesting to convert the balance of their senior apartments to assisted living units. This is an existing Type V-1 hr building and will be limited to only ambulatory persons on the upper floors. Since there is no reference in Section 310.2.2 relating to Group R-2.1 and Group R-2.2 occupancy types, if the floors and walls of each unit are properly constructed of fire-rated materials.
Can cooking appliances be used in the dwelling units?
Yes. Cooking appliances may be allowed as long as all construction requirements in Section 310.2.2 are met.
Residential Care Facilities Presentation Handout 28 June 1, 2011
Date Issued: 06-02-04 Interpretation 04-013
Topic: Requirements for Group R Occupancies
Code Section(s): § 310.10.2, California Building Code (2001)
Requested by: Dennis Lockard, Fire Marshal, PO Box 1768, Newport Beach, CA 92658- 8915
Section 310.10.2 requires that Group R, Divisions 2.1.1, 2.2.1 and 2.3.1 occupancies be provided with at least one manual pull station to activate a distinctive fire alarm signal audible throughout the facility.
1. Is the manual pull station required to be listed by the State Fire Marshal?
Yes. A manual pull station is a fire alarm device. Per Section 13114(b) of the California Health and Safety Code, all fire alarm devices must be approved and listed by the State Fire Marshal.
2. Is the device providing the audible signal required to be listed by the State Fire Marshal?
If the device is designed or constructed to be a fire alarm device, then it must be approved and listed by the State Fire Marshal. If it is not a fire alarm device then it would not have to be listed by the State Fire Marshal but it would need to produce a distinctive sound audible throughout the facility.
Date Issued: January 6, 2006 Interpretation 05-025
Topic: R-2 Facilities with multiple housing units
Code Section(s): 2001 California Building Code, Section 310
Requested by: Mark McCormick, Deputy Chief/Fire Marshal, Santa Rosa Fire Department, 955 Sonoma Avenue, Santa Rosa, CA 95404
1.) California Building Code – 2001 edition, Section 310 – Requirements for group R Occupancies, Division 2.1 states, “Residentially-based, licensed facilities accommodating more than six non-ambulatory clients. CBC 203 defines a “building” as “any structure as to which state agencies have regulatory power, used or intended for supporting or sheltering any use or occupancy ” CBC Chapter 2 does not define “facility” however, CBC 1102A.6F defines “facility” as a building, structure, room, site, complex or any portion thereof, that is built, altered, improved to serve a particular purpose.
In the case of a campus style “facility” owned by a single entity which is requesting to be licensed for more than 6 non-ambulatory clients, and there are several separate buildings comprising no more than 5 independent residential living units (townhouse style) with staff working from another separate building, is it correct for the AHJ to classify this facility as an R-2.1 and/or is it the intent of the code to classify this “facility” as an R-2.1 since the “facility” desires to house and provide service/care for more than 6 non-ambulatory clients?
The word “facility” would constitute the entire campus. If the provider requested a single license for the entire facility, and the number of non-ambulatory clients exceeds six, the facility would be classified as an R-2.1. Each residential housing unit with six or less residents would be classified as an R-2.1.1. However, individual living units that are part of a larger facility and depend on each other for evacuation assistance would be required to have an approved manual fire alarm system throughout the facility.
2.) CBC 1007.6.3.1.1 requires a minimum of two exits from buildings classified as R-2 occupancies. In the case of a building constructed in a “townhouse” style where there are 5 individual residential units, (Type V-N) separated by a one hour
Residential Care Facilities Presentation Handout 29 June 1, 2011
occupancy separation, each unit has one exit door (front door) where the sleeping room exits through the living/kitchenette room to the front door.
Is it the intent of the code that only one exit from each living space complies with the CBC 1007.6.3.2 for the arrangement of exits or would a second exit be required from the sleeping room to the outside or through another exit for non-ambulatory clients?
Each unit within the 5 unit building must have two exits as per 2001 California Building Code, Section 1007.6.3.1.1. Bedrooms in units housing non-ambulatory clients must comply with exiting arrangements as per Section 1007.6.3.2.2
Date Issued: 8/11/06 Interpretation 05-043
Topic: R-2.2 Occupancies
Code Section(s): Section 13131.5 California Health & Safety Code; Table 5b, California Building Code (2001 ed).
Requested by: Phillip Kudelka, Architect, PK Architecture, 22663 Collins Street
Woodland Hills, Ca. 91367
Building analysis:
Existing 4 story, Type V-1 hour, sprinklered
R-2.1 on first and second floors
R-2.2 on the third floor
R-1 on the fourth floor
Based on the above building analysis, can a residential care occupancy (Group R- 2.2) having six or less non-ambulatory clients be housed on the third floor?
Normally, the answer would be yes. However, in this case you have other issues to resolve. First, the R-1 could not be on the fourth floor. Table 5-B, limits R-1’s of Type V 1-hour construction to three stories. You cannot use sprinklers for an additional story as the sprinklers are already required by the R-2.1. Also, in this particular case, the R-2.1 requirements prevail. California Health and Safety Code, Section 13131.5 would require that in buildings that are three to five stories and house R-2.1 occupancies, the entire building be of Type II fire resistive construction and fully sprinklered. Consequently, as your building is a Type V 1-hour construction, you cannot use this building as you intend.
Date Issued:8-24-07 Interpretation 07-080
Topic: Group R Division 2.1.1 or 2.2.1
Code Section(s): 2001 California Building Code Section 415A
Requested by: Richard Friend, Friends Home Care, 31416 Chemin Chevalier,
Temecula, CA 92591
The title of Section 415A of the 2001 Building Code reads, "RESIDENTIALLY-BASED, LICENSED FACILITIES IN A NON-SPRINKLERED GROUP R, DIVISION 2.1.1 AND 2.2.1 OCCUPANCY HOUSING A BEDRIDDEN CLIENT" (underscoring supplied). Section 415A.1.1 goes on to state that "The purpose of this chapter is to provide a minimum level of fire and life safety protection for a bedridden client, as defined in Section 203, housed in a non-sprinklered, Group R, Division 2.1.1 or 2.2.1 Occupancy" (underscoring supplied).
1. Does Section 415A or any provisions thereof apply to Group R, Division 2.1.1 Occupancies that have been retrofitted with NFPA type 13D automatic fire sprinkler systems?
No. This section of the California Building Code applies to NON-SPRINKLERED facilities that are housing a bedridden client; therefore the facility would not have to comply with any of the provisions of 415A.
page30image25112 page30image25272
Residential Care Facilities Presentation Handout 30 June 1, 2011
2. If Section 415A does not apply to sprinklered R2.1.1 facilities, are the client bedrooms in those sprinklered R2.1.1 facilities considered approved for bedridden clients?
Yes. Keeping in mind that two exits are required and at least one of the exits must conform to the four exiting criteria set forth in §1007.6.3.2.2.
Date Issued: 1/22/08 Interpretation 07-144
Topic: Group R, Div 6.2 Location On Property
Code Section(s): 2001 CBC Section 317A and Table 5A
Requested by: Steve Bunting, Newport Beach Fire Department
Do the exterior wall and opening protection requirements in Table 5A for the Group R, Division 1 occupancy group apply to Group R, Division 6.2 occupancies?
Yes, when the exterior wall is located 3 or more feet from the property line.
Does Section 317A allow the exterior wall of a Group R, Division 6.2 which is located 3 feet or more from the property line to be non-rated and have openings?
2001 CBC Section 317A does not apply to exterior walls of a Group R 6.2 located 3 feet or more from the property line.
Date Issued: October 3, 2007 Interpretation 07-152
Topic: Bedridden Residents in Residential Care Facilities for the Elderly (RCFE) Group R-2.1 Occupancies
Code Section(s): 2001 California Building Code Section 310
Requested by: State Fire Marshal Residential Care Facilities Advisory Committee Health and Safety Code, Section 1569.72 (c) allows bedridden persons to be admitted to and remain in RCFE that maintain a fire clearance. Furthermore, it states that a fire clearance shall be issued to an RCFE, in which a bedridden person as determined by the Department of Social Services (DSS) resides if either of the following conditions are met:

1. The fire safety requirements are met.
2. Alternative methods of protection are approved.
Health and Safety Code, Section 13131.5 (b) prescribes the minimum building standards for a non-ambulatory occupancy in two story RCFEs:
Health and Safety Code, Section 13131.5 (b) All of the following building standards shall apply to any two-story building housing non-ambulatory persons on a second floor, which is operated as a residential care facility for the elderly and licensed to care for more than six persons:
(1) The entire building shall have installed a State Fire Marshal approved fully automatic fire extinguishing system, designed and installed in accordance with Section 2-3801 (d) of Chapter 2-38 Part of Title 24 of the California Code of Regulations (Title 24, Part 2 2001 California Building Code).
(2) The entire building shall have installed a State Fire Marshal approved and listed automatic fire alarm system.
(3) The entire building shall be of at least Type V one-hour fire resistive construction, as described in Chapter 2-22 of Part 2 of Title 24 of the California Code of Regulations (Title 24 Part 2001 California Building Code).
(4) A building with individual floor areas over 6,000 square feet per floor shall have an approved smoke barrier dividing the floor approximately in half, without regard to whether direct exiting is available from each dwelling unit.

Residential Care Facilities Presentation Handout 31 June 1, 2011
(5) The entire building shall have at least two sets of enclosed stairways.
RCFEs, as described in the Health and Safety Code, have been defined in the

2001 edition of the California Building Code (CBC), as R-2.1, R-2.1.1, R-2.2 and R- 2.2.1 Occupancies. The requirements are codified in the 2001 CBC, Section 310 – Group R Occupancies. However, the requirements for the R-2.1 Occupancy Group (RCFE), specifically addresses non-ambulatory residents and is silent in regard to the pertinent building standards allowing bedridden residents in an RCFE, R-2.1 Occupancy, which leads to the following question:
• Can bedridden residents be housed in an R-2.1 Occupancy Groups (RCFEs)?
Yes. Provided the minimum standards for R-2.1 Occupancies are met, fire clearance shall be granted to all applicants seeking to house and/or serve non-ambulatory and/or bedridden residents in an RCFE. CBC Section 310.1 Group R Occupancies defined, Division 2.1 to include, among other things, Residential Care Facilities for the Elderly and Residential Care Facilities for the Chronically Ill.
Furthermore, CBC Section 310.2.2 allows bedridden residents in similar R occupancies (R2.3 and R2.3.1) to be housed above the first floor provided there is construction of not less than one hour fire resistive construction throughout.
The forthcoming 2007 California Building Code based on the 2006 edition of the International Building Code with amendments reconciles the requirements of the Health and Safety Code, as well as, the 2001 CBC. R-2.1 and R-2.3 Occupancies are combined under a single I-1 Occupancy.

Section 308.2 of the 2007 California Building Code, (Effective January 2008) as follows: Group I-1. This occupancy shall include buildings, structures or parts thereof housing clients on a 24 hour basis, who because of age, mental disability or other reasons, live in a supervised residential environment that provides personal care services.
This occupancy may contain more than six non-ambulatory and/or bedridden clients. This group shall include but not be limited to, the following:
Assisted living facilities such as: Residential Care Facilities, Residential Care Facilities for the Elderly (RCFEs), Congregate Living Health Facilities, Group homes, Residential Care Facilities for the Chronically Ill, and Congregate Living Health Facilities for the Terminally Ill.

Date Issued: 1/22/08 Interpretation 07-154
Topic: Door requirements for a Group R 2.1.1 and 2.2.1
Code Section(s): 415A.4
Requested by: Frank Burgett, Hazard Reduction, Riverside County Fire Dept., Fire Prevention Technician
Code Interpretation reference Door and Hardware requirements in Group R 2.1.1 and 2.2.1 Occupancy housing “A” Bedridden client.
In Section 415A.4 it refers to bedridden clients’ sleeping room shall be a self-closing, positive latching 1 3/8” solid wood door with a gasket.
Does a solid 1 3/8” solid wood door with decorative carving (i.e. paneled door) qualify. The thickness has now decreased in areas of the carving below 1 3/8”?
No. The code specifically requires a minimum of 1 3/8” solid wood core .
Does a twenty minute fire rated door with or without decorative carving (i.e. paneled door) installed by a professional or property owner with a gasket meet the intent of a 1 3/8” solid wood door?
Yes. A 20 minute rated door with a gasket would meet this requirement.
Residential Care Facilities Presentation Handout 32 June 1, 2011
Date Issued: 1/22/08 Interpretation 07-158
Topic: Audible Fire Alarm Signals Throughout the Building
Code Section(s): CFC 1006.3.3.3.1
Requested by: David Burkhart, Code Consultants, Inc., 1804 Borman Circle Drive Saint Louis, MO 63146
Does section 1006.3.3.3.1 of the 2001 California Fire Code (CFC) require that buildings have an audible fire alarm signal throughout the building?
Yes or in designated portions of the building when approved by the Authority Having Jurisdiction.
Date Issued: May 9, 2008 Interpretation 08-014
Topic: Does a sliding glass door meet the requirement for an exit
Code Section(s): 2001 CBC 415A
Requested by: Rob Ball, Fire Marshal, Rancho Cucamonga Fire Protection District
10500 Civic Center Drive, Rancho Cucamonga, CA 91730
The following is a formal request for a State Fire Marshal Code Interpretation regarding door requirements when an existing non-sprinklered, six or fewer non- ambulatory residential care facility (R-2.1.1) wishes to house bedridden client.
The pertinent code sections are: Section 415A of the 2001 California Building Code. Section 415A.3 says that “a direct exit to the exterior of the residence shall be provided from the client sleeping room.” Section 415A.4 goes on to discuss the doors (plural) serving the bedridden client’s sleeping room. That section says, “Doors to a bedridden client’s sleeping room shall be of a self-closing, positive latching 1-3/8 inch solid wood door. Doors shall be maintained self-closing or shall be automatic closing by actuation of a smoke alarm in accordance with Section 713.” Given that: 1) A direct exit to the exterior from the client’s sleeping room is required, 2) Doors (plural) serving the client’s sleeping room have to be self-closing, positive latching 1-3/8” solid wood doors, and 3) There is no distinction made in Section 415A.4 between interior and exterior doors, was it or is It the intent of the code to allow a sliding glass door to meet the “direct exit to the exterior” requirement so long as the sliding glass door meets the criteria in Sections 415A.5 and 415A.6?
Yes.
Is the answer to this question the same for a new facility of this type that is subject to the provisions of Section 425.8.3.3 of the 2007 California Building Code?
Yes, except, current code requires the exterior door to be operable from both the inside and the outside by the facility staff.
Note: If additional hardware that is used on a sliding glass door to allow it to be operable from the inside and outside by staff impedes the 32” clear width than the sliding glass door cannot be used.

Date Issued: May 9, 2008 Interpretation 08-021
Topic: New classification of an R6.1.1
Code Section(s): 2007 California Building Code 310 and 907.2.10.3
Requested by: Gregory Lake, Supervising Inspector, Code Development and Enforcement, Sacramento Metro Fire
1. What is the new classification of an R-6.1.1? CBC 310, R-3.1 Occupancies are for facilities with 6 or fewer clients, but the section does not mention Social Rehab as one of the possible uses. (CBC 310 indicates that R-4 Occupancies are for more than
Residential Care Facilities Presentation Handout 33 June 1, 2011
6 clients, but specifically indicates Social Rehab facilities such as: halfway houses as a possible use.)
Under the 2007 CBC an R-6.11 would be classified as an R-3.1.
Date Issued: May 9, 2008 Interpretation 08-022
Topic: Do existing R-4’s have to meet current code because of a required biannual license renewal
Code Section(s): 2007 CBC Section 111.1
Requested by: C. Edward Dilkes, Attorney at Law, 2443 Park Oak Drive, Hollywood, CA 90068

Does Section 111.5.1 of the 2007 California Building Code prohibit enforcement of newly created provisions of the Building Code and Fire Code in situations where the structure in question is: (1) either an I-1 or R occupancy Group, (2) the structure was occupied and used as an I-1 or R occupancy prior to the effective date of the 2007 amendments to the Code, (3) no change in occupancy will occur, and (4) there have been no structural alterations?
Yes, existing Group I-1 and R occupancies shall be inspected under the code in effect at time of licensing.
Reference: CBC Section 111.5.1 Existing Group I-1 or Group R Occupancies. Licensed 24- hour care in a Group I-1 or Group R occupancy in existence and originally classified under previously adopted state codes shall be re-inspected under the appropriate previous code, provided there is no change in the use or character which would place the facility in a different occupancy group.

Date Issued: May 13, 2008 Interpretation 08-025
Topic: Wireless inter-connected smoke alarms for Group R occupancies
Code Section(s): 2007 California Building Code 907.2.10.4
Requested by: Gregory Lake, Supervising Inspector, Code Development and Enforcement, Sacramento Metro Fire
1. Can SFM-listed smoke alarms that are AC hardwired but have radio transmitted interconnection be used to satisfy CBC 907.2.10.3?
Yes. This can be applied to an R3.1
2. Does 907.2.10.4 prohibit their use since testing the interconnecting wires is part of the acceptance test?
No
Date Issued: 2/2/2009 Interpretation 08-047
Topic: R3.1 Clarifications of Sprinklers and Exiting
Code Section(s): 2007 California Building Code Section 425
Requested by: Gregory Lake, Supervising Inspector, Sacramento Metropolitan Fire District, 3012 Gold Canal Dr., Rancho Cordova, CA 95670
R-3.1 Occupancies
1. Where residential fire sprinklers have been installed throughout a single family dwelling per NFPA 13D:
a. CBC 425.3.4 - Can residential fire sprinklers be used for substitution of 1-hour fire- resistance-rated construction required in this section?
No. Per 2007 CBC Chapter 6 Table 601 Footnote e.
Residential Care Facilities Presentation Handout 34 June 1, 2011
b. CBC 425.8.2.1 – Minimum of 2 exits – Can residential fire sprinklers be used to mitigate this section where a second means of egress leads to an enclosed back yard with no access to the public way or a safe area?
No. The 2007 CBC does not have provisions for this allowance.
c. CBC 425.8.3.2 – Do fire sprinklers mitigate the need for non-ambulatory exiting in this section?
No. The 2007 CBC does not have provisions for this allowance.
d. CBC 425.8.3.2 and CBC 903.2.7 – Can fire sprinklers be used to mitigate the required 2nd exit from second floors housing non-ambulatory clients?
No. The 2007 CBC requires fire sprinklers on the second floor; therefore, there are no provisions for this allowance.
e. CBC 425.8.3.3 – Do fire sprinklers mitigate the need for bedridden exiting for all bedrooms with “a” bedridden client?
2007 CBC 425.8.3.3 does not apply where there is more than one bedridden client.
2. CBC 425.8.3.2 - Are bathroom doors and closet doors in the egress hallways of R- 3.1 occupancies required to be solid core doors as required for the door at the mouth of the hallway because these areas are “common area” separation doors? No. 2007 CBC Section 425.8.3.2 addresses the hallway door separating the bedrooms from the common areas.
Date Issued: 9/18/08 Interpretation 08-050
Topic: Residential Care Facility I-1
Code Section(s): 2007 California Building Code Section 308.2
Requested by: SFM Residential Care Advisory Committee
For I-1 occupancies section 308.2 states “this occupancy may contain more than six non-ambulatory and/or bedridden clients”.
Was it the intent of the code due to the use of the word MAY to allow the AHJ the ability to deny an 850 fire clearance request for bedridden?
No. The intent of this section was not directed at the fire service. It was the intent of the code to allow the licensee the option of retaining non-ambulatory and/or bedridden in the facility as long as all the required fire & life safety requirements were met. If the code were to use the term “shall” in the sentence each facility would be required to retain bedridden clients in their facility.
Date Issued: 10/1/08 Interpretation 08-060
Topic: Existing R-2.1.1 or R-2.2.1 Occupancies (6 or less)
Code Section(s): 2007 California Building Code, Section 111.5.1
Requested by: State Fire Marshal Residential Care Advisory Committee
Is a Residential Care Facility licensed for 6 or fewer clients prior to January 1, 2008 required to meet the 2007 California Building Code if the client capacity is changed to increase the number of non-ambulatory or bedridden beds?
Yes. The following statements apply to your question and clarify the intent of Section 111.5.1, 2007 CBC as it relates to residential care facilities housing six or less clients.
1. All existing facilities can remain under the 2001 CBC as long as there are no changes to their license relative to non-ambulatory or bedridden.
2. All existing facilities adding non-ambulatory and/or bedridden shall meet the requirements of the 2007 California Building Code.
Note: Effective as to date of issuance above

Residential Care Facilities Presentation Handout 35 June 1, 2011
Date Issued 12/19/08 Interpretation 08-073
Topic: RCFE Exiting Requirements
Code Section(s): 2007 California Building Code Section 425.8.3.3
Requested by: Matt Sather, Owner, Shield Fire Protection, 27052 Lost Colt Dr.
Laguna Hills, CA 92653
When a facility with 6 non-ambulatory clients adds a residential fire sprinkler system to meet the requirements for 6 bedridden, are the CBC 2007 Section 425.8.3.3 requirements for a single bedridden client also required to be installed in each of the six bedridden rooms?
No. However, keep in mind that two exits are required and at least one of the exits must conform to the four exiting criteria set forth in 2007 California Building Code Section 425.8.3.2.
esidential Care Facilities Presentation Handout 37 June 1, 2011
page38image376
Residential Care Facilities Presentation Handout 38 June 1, 2011
California State Fire Marshal Information Bulletin April July 25, 2001
BEDRIDDEN CLIENTS IN
RESIDENTIAL CARE FACILITIES
Current SFM regulations do not address the placement of bedridden clients in a residential setting. However, on January 1, 2001, a new California statute (SB 1896-
Ortiz) became effective which amended existing sections of the California Health and Safety Code to allow the placement of bedridden persons in residential care facilities licensed by the California Department of Social Services. As provided by this new law,
this means that bedridden clients can now be placed in residential care facilities.
The scope of the statute provides for the following:
1. Creation of a new definition for “bedridden”.
2. Provides the Department of Social Services with the authority to determine the bedridden status of persons (in consultation with the Director of Developmental Services).
3. Allows bedridden persons in residential care facilities if

(A) The facility receives a fire clearance by meeting applicable requirements; or, (B) Alternative methods of protection are approved by the AHJ.
4. Requires that the State Fire Marshal and the Department of Social Services adopt regulations to meet the mandate of the statute.
5. Requires that the State Fire Marshal identify procedures for requesting the approval of alternate means of providing equivalent levels of fire and life safety protection.
6. Requires that the State Fire Marshal provide a written response to a code interpretation of the new regulations within 45 days of request.
SFM is currently drafting the necessary regulations. In the interim, SFM recommends that fire officials work with any facility in their jurisdiction to achieve an acceptable alternate means of protection until the new regulations are in place.
Questions regarding this issue may be addressed to SFM Code Development &
Analysis Division by telephoning Gini Krippner at (916) 327-7672

California State Fire Marshal
Residential Care Facilities Presentation Handout 39 June 1, 2011
Information Bulletin October 10, 2001
BEDRIDDEN CLIENTS IN
RESIDENTIAL CARE FACILITIES
Current SFM regulations do not address the placement of bedridden clients in a residential setting. However, on January 1, 2001, a new California statute (SB 1896-
Ortiz) became effective which amended existing sections of the California Health and Safety Code to allow the placement of bedridden persons in residential care facilities licensed by the California Department of Social Services. As provided by this new law,
this means that bedridden clients can now be placed in residential care facilities.
The scope of the statute provides for the following:
1. Creation of a new definition for “bedridden”.
2. Provides the Department of Social Services with the authority to determine the bedridden status of persons (in consultation with the Director of Developmental Services).
3. Allows bedridden persons in residential care facilities if
(A) The facility receives a fire clearance by meeting applicable requirements;
or,
(B) Alternative methods of protection are approved by the AHJ.
4. Requires that the State Fire Marshal and the Department of Social Services adopt regulations to meet the mandate of the statute.
5. Requires that the State Fire Marshal identify procedures for requesting the approval of alternate means of providing equivalent levels of fire and life safety protection.
6. Requires that the State Fire Marshal provide a written response to a code interpretation of the new regulations within 45 days of request.
SFM is currently drafting the necessary regulations. In the interim, SFM recommends that fire officials work with any facility in their jurisdiction to achieve an acceptable alternate means of protection until the new regulations are in place.
Questions regarding this issue may be addressed to SFM Code Development &
Analysis Division by telephoning Gini Krippner at (916) 327-7672

California State Fire Marshal Information Bulletin April 10, 2007
Residential Care Facilities Presentation Handout 40 June 1, 2011
BEDRIDDEN PERSONS IN RESIDENTIAL CARE FACILITIES FOR THE ELDERLY (RCFE’S) HOUSING 7 or MORE NON-AMBULATORY CLIENTS
The Office of the State Fire Marshal has received numerous questions concerning the admission and retention of “bedridden” persons in a 7 or more Licensed Residential Care Facility for the Elderly (RCFE). The purpose of this “Information Bulletin” is to clarify this issue and prevent the unnecessary relocation of bedridden persons.
Health and Safety Code Section 1569.72(a) indicates that no bedridden persons as determined by the Department of Social Services (other than for a temporary illness or one who is recovering from surgery) shall be admitted or retained in a residential care facility for the elderly (RCFE).
However, Section 1569.72(c), a newer statue resulting from SB 1896, allows bedridden persons to be admitted to and remain in residential care facilities for the elderly that secure and maintain a fire clearance. It states that a fire clearance shall be issued to a facility in which a bedridden person as determined by the Department of Social Services (DSS) resides if either of the following conditions are met:
(1) The fire safety requirements are met.
(2) Alternative methods of protection are approved.

(1) The fire safety requirements are met. If Item 1 is used to obtain the fire clearance,
all other fire safety requirements for the specific R-2.1 occupancy (7 or more non-ambulatory) for the elderly as prescribed in the current 2001 edition of the California Building Code shall apply. It should be noted that the current code prohibits “bedridden” client sleeping rooms other than those used for “temporary bedridden” be located above or below the first floor.

(2) Alternative methods of protection are approved. If Item 2 is used to obtain the fire clearance for bedridden residents above the first floor, the facility can request the enforcing agency to grant approval for an alternate material, design or method of construction that shall be approved where the enforcing agency finds that the proposed design is satisfactory and complies with the intent of the provisions of the code. This request is subject to final approval by the enforcing agency on a case by case basis. Example: utilization of the recently adopted 2007 California Building Code which does not prohibit bedridden persons from being placed and/or retained on or above the first floor or any other alternate means of protection that is acceptable to the enforcing agencies that provides for an equal or better degree of protection. The recently adopted code can be found at http://osfm.fire.ca.gov/pdf/codeadoption/part2expresstermsfinal.pdf .
For questions and information regarding this Information Bulletin, please contact Chief Ernie Paez at (626) 305-1908 or ernie.paez@fire.ca.gov
page41image22416 page41image22576 page41image22736 page41image22896 page41image23056 page41image23216 page41image23376 page41image23536 page41image23696 page41image23856
Residential Care Facilities Presentation Handout 41 June 1, 2011
page42image400 page42image568
California State Fire Marshal Information Bulletin
Exterior Ramps Group R-3.1
Issued: March 10, 2009
This Information Bulletin is being issued to clarify a State Fire Marshal regulation contained in California Code of Regulations, Title 24, Part 2 California Building Code (CBC). This Information Bulletin specifically addresses the requirements contained in CBC Section 425.8.5 Changes in Level relating to ramps in Group R-3.1 occupancies (Residential Care Facilities for 6 or fewer clients) and enforcement responsibilities of the local fire official.
Over the past several years the issue of mandating ramps on the exterior of Group R-3.1 occupancies has been a concern for fire and building code officials. The Office of the State Fire Marshal (OSFM) has posted several code interpretations on this issue (00-019 & 02-025) and most recently the question arose regarding the 2007 California Building Code. During the rulemaking process to create the 2007 California Building Code, the OSFM had not revised the intent for changes in level in Group R-3.1 occupancies (Section 425.8.5), and further does not require changes in level for the exterior to be made by means of a ramp.
Re-searching back to previous editions of the CBC, the language has remained the same, and the intent remains the same; in that, it is not the responsibility of the local fire official to enforce exterior exit ramps as these code sections apply to the interior changes of level in the facility only. Enforcement of other provisions of the CBC relating to accessibility that may require exterior ramps are typically enforced by the local building official. Questions or comments regarding the application of Chapter 11A accessibility provisions should be referred to the California Department of Housing and Community Development and/or your local Building Official.
For more information please visit our website http://osfm.fire.ca.gov
page42image16112
Residential Care Facilities Presentation Handout 42 June 1, 2011
page43image400 page43image832 page43image1264 page43image1696
Residential Care Facilities Presentation Handout 43 June 1, 2011
Additional Pre-Inspection Information for the Fire Inspector:
In order to provide the most complete list of requirements, please provide the following information:
Facility Name: ___________________________Assessors Parcel Number:________________________ Residents will be sleeping on
page44image2888
Type of Facility:
Residential Building
Commercial Building
Number of Stories in Building: __________

page44image4512 page44image4936
Age Group:
18-64 years
Number of Residents:
1 - 6
7 or More

Applicant Information
Elderly
Fire Sprinklers ________which floors in building?
___ Yes ___ No _______________
page44image8752
___ Yes ___ No _______________
page44image9520 page44image9680 page44image10104
Ambulatory
______
______
Non-Ambulatory_____Bedridden
page44image11728 page44image11888
______
______
______
______
page44image13400 page44image13824
Name:________________________________Day Phone: (
Mailing Address:_______________________________City:___________________Zip:____________ By: (Print)__________________________________Signed:___________________________________ E-Mail Address ______________________________________________________________________

Owner Licensee Agent for Owner Contractor
page44image15560 page44image15984 page44image16408 page44image16832
Residential Care Facilities Presentation Handout 44
June 1, 2011
)__________ Fax: (
)___________
page45image400 page45image832 page45image1264 page45image1696
Residential Care Facilities Presentation Handout 45 June 1, 2011
Residential Care Facilities (Group R-2.1)
Inspection Checklist (2010 Codes)
(Group 1-1 = More than 6 Non-Ambulatory or bedridden. Regardless of licensing agency)
page46image3144 page46image3304
OK
CN
NA
page46image4968 page46image5128 page46image5288 page46image5768 page46image5928 page46image6088 page46image6248
1.
Minimum Construction:
Type V-1 Hour construction. Max of 10,500 sq. ft.—3 stories. Nonambulatory clients to be limited to the first two stories. CBC Section 425.4.1 & Table 503.

page46image8856 page46image9280 page46image9704 page46image10288 page46image10448 page46image10608 page46image10768
2.
Smoke Barriers:
a. Required where individual floor area exceeds 6,000 sq. ft. Area of a single smoke compartment shall not exceed 22,500 sq. ft. and travel distance to an exit or smoke barrier wall shall not exceed 200 feet. CBC, Sec. 425.5.1
Exception: One story facilities housing more than six non-ambulatory elderly where the buildings have direct exits from each dwelling unit. H & S code, Section 13131.5.(a)(#4)
b. Smoke barrier framing to be covered with noncombustible material with thermal barrier index of not less than 15. CBC 425.5.2
page46image16440 page46image16864 page46image17288 page46image17872 page46image18032 page46image18192 page46image18352
3.
page46image19120 page46image19544 page46image19968 page46image20392 page46image20552 page46image20712
4.
Automatic Fire Sprinkler Protection:
Fire Sprinkler System in accordance with NFPA 13. CBC Sec. 903.2.8.

page46image22856
Smoke Alarms:
Required in each sleeping area and in the corridor or area giving access to each separate sleeping area.
Exception: Smoke alarms not required in sleeping rooms when the sleeping rooms are protected by smoke detectors which are part of an automatic smoke detection system.
CBC Sec. 425.7.3 and 907.2.11.2.

page46image26088 page46image26512 page46image26936 page46image27520 page46image27680 page46image27840 page46image28000
5.
Carbon Monoxide Alarms:
Required in R-2.1’s which have dwelling units or sleeping units which have fuel-burning appliances installed within the unit. Carbon monoxide alarms shall be connected to the building wiring and have battery back-up. Where there is more than one alarm within the unit, all alarms shall be interconnected so that when one alarm is activated all alarms within the unit shall sound. CBC Sec. 420.1
page46image32592 page46image33016 page46image33440 page46image34024 page46image34184 page46image34344 page46image34504
6.
page46image35272 page46image35696 page46image36120 page46image36544 page46image36704 page46image36864
7.
Fire Alarm:
a. A complete automatic and manual fire alarm system shall be provided in accordance with CBC Section 907.2.9.3. This requirement is in addition to the smoke alarms required by CBC Section 425.7.3
Exception: Buildings housing non-ambulatory clients only on the first floor and protected throughout by all of the following:
1. An approved supervised automatic fire sprinkler system installed in

accordance with NFPA #13. Activation of sprinkler system shall
sound the building fire alarm system.
2. A manual fire alarm system.
3. Smoke alarms as required by CBC Sec. 907.2.11.
b. Strobes shall be provided in public areas, common use areas, sleeping rooms and protective care facilities housing hearing impaired clients. CBC Section 907.5.2.3, 907.5.2.3.1 & 907.5.2.3.3.
page46image44640
Exits: Two Exits required. CBC Sec. 425.8.2.1.
page46image45488 page46image45912 page46image46336 page46image47184 page46image47344 page46image47504 page46image47664 page46image47824
8.
Corridor Construction:
page46image50616 page46image50776 page46image50936 page46image51096 page46image51256 page46image51416 page46image51576 page46image51736
Residential Care Facilities Presentation Handout 46 June 1, 2011
page47image1904 page47image2064 page47image2384 page47image2544 page47image2704 page47image2864 page47image3184 page47image3344 page47image3504
9.
page47image4112 page47image4536 page47image4960 page47image5384 page47image5544 page47image5704
10.
page47image6472 page47image6896 page47image7320 page47image7744 page47image7904 page47image8064
11.
Hallways/corridors serving 7 or more shall be 1-hour fire resistive with door openings protected by 20-minute fire rated assemblies. Doors to be maintained self-closing or automatic-closing by activation of a smoke detector. Glazed openings to be labeled 3⁄4 hour fire- rated assemblies. Table 1018.1.
Exception: In sprinklered buildings, rated corridor doors to client rooms do not require self-closers. (See CBC Sec. 425.8.4.2)
page47image12456
Corridor Width:
60 inches on floors housing non-ambulatory clients and 44 inches on floors housing only ambulatory clients. CBC Sec. 425.8.4.2.

page47image14232
Intervening Rooms:
Corridors shall not be interrupted by intervening rooms. CBC Sec. 1018.6.
Exception 1: Foyers, lobbies and reception rooms shall not be considered intervening rooms.
page47image16416
Exit Enclosure:
Two enclosed exit stairways remotely located shall be required if 7 or more non-ambulatory clients are located above the first floor. CBC Sec. 425.8.6.1.
page47image18448 page47image18872 page47image19296 page47image19880 page47image20040 page47image20200 page47image20360
12.
Delayed Egress:
Allowed if conforming to requirements of CBC Sec. 1008.1.9.7.

page47image21920 page47image22344 page47image22768 page47image23352 page47image23512 page47image23672 page47image23832
13.
Bedridden Clients:
Allowed for facilities licensed after Jan. 1, 2008. See definition in CBC Section 310.1.

page47image25696 page47image26120 page47image26544 page47image27128 page47image27288 page47image27448 page47image27608
14.
Exit Signs:
Required as per CBC Section 1011.1

page47image29048 page47image29472 page47image29896 page47image30480 page47image30640 page47image30800 page47image30960
15.
Floor Level Exit Signs:
Required as per CBC Section 1011.6.
Exception: Where exit path marking is provided
page47image32864 page47image33288 page47image33712 page47image34296 page47image34456 page47image34616 page47image34776
16.
Exit Path Marking:
Required as per CBC Section 1011.7
Exception: Where floor level exit signs are provided
page47image36680 page47image37104 page47image37528 page47image38112 page47image38272 page47image38432 page47image38592
17.
Tactile Exit Signs:
Required as per CBC Section 1011.3.

page47image40232 page47image40656 page47image41080 page47image41664 page47image41824 page47image41984 page47image42144
18.
Emergency Lighting:
Required as per CBC Section 1006.3.
Exception: Client sleeping rooms.
page47image43848 page47image44272 page47image44696 page47image45280 page47image45440 page47image45600 page47image45760
19.
Fire Extinguishers:
Required as per CFC Sections 906.1

page47image47200 page47image47624 page47image48048 page47image48896 page47image49056 page47image49216 page47image49376
20.
Exit ramps:
Required as per CBC Section 1003.5

page47image50816 page47image51240 page47image51664
page47image52568 page47image52888 page47image53048 page47image53368 page47image53688 page47image54008 page47image54328 page47image54648 page47image54968 page47image55128 page47image55448 page47image55768 page47image55928
Residential Care Facilities Presentation Handout 47 June 1, 2011
Residential Care Facilities (Group R-4)
Inspection Checklist (2010 Codes)
(Group R-4 = More than 6 Ambulatory, Regardless of licensing agency) May have up to 6 non-amb or bedridden
page48image3488 page48image3648 page48image3968 page48image4128 page48image4288 page48image4608 page48image5032 page48image5456 page48image5880 page48image6040 page48image6200 page48image6520 page48image6944 page48image7368 page48image7792 page48image7952 page48image8112
3.
Smoke Barriers:
a. Required where individual floor area exceeds 6000 sq. ft. Area of a single smoke compartment shall not exceed 22,500 sq. ft. and travel distance to an exit or smoke barrier wall shall not exceed 200 feet. CBC, Sec. 425.5.1
b. Smoke barrier framing to be covered with noncombustible material with thermal barrier index of not less than 15. CBC 425.5.2

OK
CN
NA
page48image13784 page48image13944 page48image14104 page48image14584
1.
Minimum Construction:
Type V-N Maximum of 7000 sq. ft.—3 stories. Higher if different construction. Table 503.
Exception 1: Where non-ambulatory clients are housed above the first floor, or there is more
than 3000 Sq. Ft. of area above the first floor or housing more than 16 clients at this level, the
construction shall be 1-hour fire resistive throughout. CBC Sec. 425.3.5.
Exception 2: Facilities housing non-ambulatory elderly clients shall be at least Type V, 1-hour throughout. CBC, Section 425.3.6
page48image19968
2.
page48image20736
Automatic Fire Sprinkler Protection:
Fire Sprinkler System in accordance with NFPA 13. CBC Sec. 903.2.7. Exception 1: Protective Social Care facilities housing ambulatory persons ages 18-64 years.
Exception 2: Occupancies housing ambulatory children only none of whom are mentally ill or mentally retarded, and the building does not exceed 2 stories in height and is equipped with a complete smoke detection system.
page48image24408 page48image24832 page48image25256 page48image25840 page48image26000 page48image26160 page48image26320
4.
Smoke Alarms:
Required in each sleeping area and in the corridor or area giving access to each separate sleeping area. CBC Sec. 425.7.3 & 907.2.10.1.2
page48image28816 page48image29240 page48image29664 page48image30248 page48image30408 page48image30568 page48image30728
5.
Fire Alarms:
a
. An approved manual and automatic fire alarm system. CBC Sec. 907.2.8.4.
Exception 1: Protective social care facilities housing persons none of whom are physically or mentally handicapped or non-ambulatory and provided with manual fire alarm system.
Exception 2: Protective social care facilities provided with a sprinkler system and a manual fire alarm box that will actuate a fire alarm signal audible throughout the facility.
b. Strobes shall be provided in public areas, common use areas, sleeping rooms and protective social care facilities housing hearing impaired clients. CBC Section 907.9.1.1, 907.9.1.5.
page48image36768 page48image37192 page48image37616 page48image38200 page48image38360 page48image38520 page48image38680
6.
page48image39448 page48image39872 page48image40296 page48image40720 page48image40880 page48image41040
7.
Exits:
Two Exits required. CBC Sec. 425.8.2.1
page48image42872
Corridor Construction:
Hallways/corridors serving 11 or more shall be 1-hour fire resistive with door openings protected by 20-minute fire rated assemblies. Doors to be maintained self-closing or automatic-closing by activation of a smoke detector. Glazed openings to be labeled 3⁄4 hour fire-rated assemblies. CBC Sec. 425.8.4.1 & Table 1017.1.
page48image46032 page48image46456 page48image46880 page48image47728 page48image47888 page48image48048 page48image48208 page48image48368
8.
Corridor Width:
44 inches on floors housing only ambulatory clients. CBC Sec. 425.8.4.2.
Exception 1: Corridors serving 10 or less may be 36 inches in width. Exception 2: Corridors serving ambulatory persons only and having an
page48image51624 page48image52048 page48image52472
page48image53536 page48image53696 page48image53856 page48image54016 page48image54176 page48image54336 page48image54496 page48image54656
Residential Care Facilities Presentation Handout 48 June 1, 2011
page49image1808 page49image1968 page49image2288 page49image2448 page49image2608 page49image2768
occupant load of 49 or less may be 36 inches in width.
page49image4136 page49image4296 page49image4456 page49image4616
9.
Intervening Rooms:
Corridors shall not be interrupted by intervening rooms. CBC Sec. 1017.5
Exception 1: Foyers, lobbies and reception rooms shall not be considered intervening rooms.
page49image7368 page49image7792 page49image8216 page49image8800 page49image8960 page49image9120 page49image9280
10.
Exit Enclosure:
Two enclosed exit stairways remotely located shall be required if 7 or more non-ambulatory clients are located above the first floor. CBC Sec. 425.8.6.1.
page49image11760 page49image12184 page49image12608 page49image13192 page49image13352 page49image13512 page49image13672
11.
Delayed Egress:
Allowed if conforming to the requirements of CBC Sec. 1008.1.8.6.
page49image15384 page49image15808 page49image16232 page49image16816 page49image16976 page49image17136 page49image17296
12.
Bedridden Clients:
Allowed for facilities licensed after Jan. 1, 2008. May have up to six non- amb or 6 bedridden clients. See CBC Section 301.1 for definition of R-4 occupancies.
page49image19936 page49image20360 page49image20784 page49image21368 page49image21528 page49image21688 page49image21848
13.
Exit Signs:
Required as per CBC Section 1011.1.
page49image23400 page49image23824 page49image24248 page49image24832 page49image24992 page49image25152 page49image25312
14.
Floor Level Exit Signs:
Required as per CBC Section 1011.6.
Exception: Where exit path marking is provided
page49image27600 page49image28024 page49image28448 page49image29032 page49image29192 page49image29352 page49image29512
15.
Exit Path Marking:
Required as per CBC Section 1011.7
Exception: Where floor level exit signs are provided
page49image31800 page49image32224 page49image32648 page49image33232 page49image33392 page49image33552 page49image33712
16.
Tactile Exit Signs:
Required as per CBC Section 1011.3.
page49image35304 page49image35728 page49image36152 page49image36736 page49image36896 page49image37056 page49image37216
17.
Emergency Lighting:
Required as per CBC Section 1006.3. Exception: Client sleeping rooms.
page49image39032 page49image39456 page49image39880 page49image40464 page49image40624 page49image40784 page49image40944
18.
Fire Extinguishers:
Required as per CFC Sections 906.1 & 906.3.
page49image42576 page49image43000 page49image43424 page49image44272 page49image44432 page49image44592 page49image44752
19.
Exit ramps:
Required as per CBC Section 1003.5
page49image46304 page49image46728 page49image47152
page49image48056 page49image48216 page49image48536 page49image48856 page49image49176 page49image49496 page49image49656 page49image49816 page49image50136 page49image50456 page49image50776 page49image50936
Residential Care Facilities Presentation Handout 49 June 1, 2011
Residential Care Facilities (Group R-3.1)
Inspection Checklist (2010 Codes)
(Group R-3.1 = Six or less clients, regardless of ambulatory status, or licensing agency)
page50image3416 page50image3576
OK
CN
NA
page50image5240 page50image5400 page50image5560 page50image6040 page50image6200 page50image6360 page50image6520
1.
Minimum Construction:
Non-rated up to 3 stories. CBC Table 503. (Must be Type V 1-hour in facilities housing clients above the first floor, more than 2 stories in height or having more than 3,000 sq. feet floor area above the first floor). CBC Section 425.3.2.
In facilities housing a bedridden client, the client sleeping room shall not be located above or below the first floor. 425.3.2.
Exception: Clients who are temporarily bedridden for up to 14 days as per H&S Code. 1566.45
page50image11704 page50image12128 page50image12552 page50image13136 page50image13296 page50image13456 page50image13616
2.
Smoke Barriers: Not required.
page50image15056 page50image15480 page50image15904 page50image16488 page50image16648 page50image16808 page50image16968
3.
Automatic Sprinklers:
  1. Not required unless housing bedridden clients or housing non-ambulatory clients
    above the first floor or housing clients above the second floor. CBC 903.2.8.
  2. Not required if housing only one bedridden client and complying with Section
    425.8.3.3. CBC.
  3. An NFPA 13D system is required in new buildings where building permits and
    construction took place after January 1, 2011. CRC R313.3.
page50image22000 page50image22424 page50image22848 page50image23432 page50image23592 page50image23752 page50image23912
4.
Smoke Alarms:
page50image25168 page50image25592 page50image26016
a. b.
Required in all habitable areas of the facility including stairwells, except kitchens. CBC Section 907.2.11.2.
In all facilities housing any bedridden clients, smoke alarms shall receive their

Primary power from the building wiring and shall be equipped with battery backup. Alarms shall be interconnected so that they all sound upon actuation of a single smoke alarm. They are not required to be interconnected to a control panel. CBC Section 907.2.11.2.2.
page50image31040 page50image31200 page50image31360 page50image31520
5.
Carbon Monoxide Alarms:
1. Required in all new dwellings built after January 1, 2011. CBC 420.4.1.
Might be required by building or fire officials for existing dwellings after July 1, 2011. H&S Code 17926.

page50image34368 page50image34792 page50image35216 page50image35800 page50image35960 page50image36120 page50image36280
5.
Fire Alarm: Not required.
page50image37720 page50image38144 page50image38568 page50image39152 page50image39312 page50image39472 page50image39632
6.
Strobes:
Required in protective care facilities that house any deaf patient. Strobes shall activate upon initiation of any smoke alarm. CBC Section 907.5.2.3.5.

page50image41936 page50image42360 page50image42784 page50image43368 page50image43528 page50image43688 page50image43848
7.
page50image44616 page50image45040 page50image45464 page50image45888 page50image46048 page50image46208
8.
Exits:
Minimum of two exits are required. CBC Section 425.8.2.1.
page50image48160
Corridor Construction: Non-rated. CBC 1018.1
page50image49032 page50image49456 page50image49880 page50image50464 page50image50624 page50image50784 page50image50944
9.
Corridor Width:
Shall be 36 inches on floors housing clients. CBC Section 425.8.4.2 and 1018.2

page50image52824 page50image53248 page50image53672 page50image54256 page50image54416 page50image54576 page50image54736
10.
Intervening Rooms:
Means of egress shall not pass through more than one intervening room. A means of egress shall not pass through kitchens, storerooms, closets, garages or spaces used for similar purposes. CBC Section 425.8.3.4.
Exception: Kitchens that do not form separate rooms by construction.
page50image58128 page50image58552 page50image58976 page50image59824 page50image59984 page50image60144 page50image60304 page50image60464
11.
Exit Access:
a. Sleeping rooms used for non-ambulatory clients shall have access to one of the following exit arrangements: (Given in order of preference)
1. Direct exit from the sleeping rooms to the exterior. The exit shall have a door at least 3 feet in width and not less than 6 feet 8 inches in height. Door shall be capable of opening at least 90 degrees and shall provide at least 32 inches of clear width.
2. From sleeping room through an adjoining sleeping room with direct exit.
page50image65888 page50image66312 page50image66736
page50image67960 page50image68120 page50image68280 page50image68440 page50image68600 page50image68760 page50image68920 page50image69080 page50image69240 page50image69400 page50image69560 page50image69720
Residential Care Facilities Presentation Handout 50 June 1, 2011
page51image1424 page51image1584 page51image1904 page51image2064 page51image2224 page51image2384 page51image2704 page51image2864 page51image3024 page51image3344 page51image3768 page51image4192 page51image4616 page51image4776 page51image4936
13.
page51image5704 page51image6128 page51image6552 page51image6976 page51image7136 page51image7296 page51image7616 page51image8040 page51image8464 page51image8888 page51image9048 page51image9208
15.
3. From sleeping room through the hallway serving the sleeping and which has an exit directly to the outside. The hallway shall be separated from the rest of the house by a wall and a 1-3/8” self-closing, solid wood door. The door can be automatic closing by actuation of a smoke detector installed in accordance with Section 715.4.8.
4. From sleeping room through the hallway into another sleeping room that has an exit directly to the outside. The hallway shall be separated from the rest of the house by a wall and a 1-3/8” self-closing, solid wood door. The door can be automatic closing by actuation of a smoke detector. CBC Section 425.8.3.2.
b. Sleeping rooms used for occupancies housing only one bedridden client shall meet all of the following requirements:
  1. Sleeping room for the bedridden client shall exit directly to the exterior of the building.
  2. Interior doors to sleeping room shall be a self-closing, positive latching 1-3/8” solid wood
    Door provided with a gasket to be smoke-tight. The door can be automatic closing by
    actuation of a smoke alarm.
  3. Doors from sleeping rooms leading to an interior corridor or interior areas shall not have a
    night-latch, dead-bolt, security chain, or any similar locking devices.
  4. The exterior sleeping room door shall be operable from both the interior and exterior of the
    residence.
  5. Exterior sleeping room doors shall be at least 3 foot wide and 6 feet 8
    inches high with a clear width of 32” and capable of opening at least 90 degrees. CBC
Section 425.8.3.3.
Note: A sliding glass door can be used as the exterior exit door if it is operable from inside and outside and clear width of exit way is at least 32 inches.
If facility wants to house more than one bedridden, they have to provide sprinklers and only comply with exiting requirements for non-ambulatory.

page51image27096
12.
Floor Separation:
a. Floor separations shall be provided with non-rated smoke partition to prevent smoke travel between floors. Such partitions shall have construction equal to 1⁄2 “ gypsum board on one side of wall framing. CBC Section 425.8.7
Exceptions:
1. Occupancies with at least one exterior exit from floor occupied by patients.
2. Occupancies provided with automatic fire sprinkler systems.
b. Door openings in floor separations shall be protected by 1-3/8 inch solid wood core doors which shall be positive latching, smoke gasketed and self-closing or automatic closing by activation of a smoke detector. CBC Section 425.8.7.1.
page51image33088
Delayed Egress:
Allowed if facility meets all requirements of CBC Section 1008.1.9.7.

page51image34400
14.
Exit Signs:
Not required. CBC Section 1011.1, Exception #3

page51image36040
Tactile Exit Signs: Not Required.
page51image36912 page51image37336 page51image37760 page51image38344 page51image38504 page51image38664 page51image38824
16.
page51image39592 page51image40016 page51image40440 page51image40864 page51image41024 page51image41184 page51image41504 page51image41928 page51image42352 page51image42776 page51image42936 page51image43096 page51image43256
18.
Emergency Lighting:
Not required. CBC Section 1006.1, Exception #3

page51image45160
17.
Fire Extinguishers:
Required. CBC Section 906.1, Item #1

page51image47024
Exit ramps:
Required in facilities housing non-ambulatory clients when changes in level exceed 1⁄2 inches. CBC Section 425.8.5.

page51image48520 page51image48944 page51image49368
page51image50432 page51image50592 page51image50752 page51image50912 page51image51072 page51image51232 page51image51392
Residential Care Facilities Presentation Handout 51 June 1, 2011

page52image4712 page52image4872 page52image16048 page52image16208 page52image16368 page52image16528 page52image16688 page52image16848 page52image17008 page52image17168 page52image17928 page52image18088 page52image31112 page52image31272 page52image31432 page52image31592 page52image31752 page52image31912 page52image32072 page52image32232 page52image32392 page52image32552 page52image32712 page52image32872 page52image33032 page52image33192 page52image33352 page52image33512 page52image33672 page52image33832 page52image33992 page52image34152 page52image34312 page52image34472 page52image34632 page52image34792 page52image34952 page52image35112 page52image35272 page52image35432 page52image35592 page52image35752 page52image35912 page52image36072 page52image36232 page52image36392 page52image36552 page52image36712 page52image36872 page52image37032 page52image37192 page52image37352 page52image37512 page52image37672 page52image37832 page52image37992 page52image38152 page52image38312 page52image38472 page52image38632 page52image38792 page52image38952 page52image39112 page52image39272 page52image39432 page52image39592 page52image39752 page52image39912 page52image40072 page52image40232 page52image40392 page52image40552 page52image40712 page52image40872 page52image41032 page52image41192 page52image41352 page52image41512 page52image41672 page52image41832 page52image41992 page52image42152 page52image42312 page52image42472 page52image42632 page52image42792 page52image42952 page52image43112 page52image43272 page52image43432 page52image43592 page52image43752 page52image43912 page52image44072 page52image44232 page52image44392 page52image44552 page52image44712 page52image44872 page52image45032 page52image45192 page52image45352 page52image45512 page52image45672 page52image45832 page52image45992 page52image46152 page52image46312 page52image46472 page52image46632 page52image46792 page52image46952 page52image47112 page52image47272 page52image47432 page52image47592 page52image47752 page52image47912 page52image48072 page52image48232 page52image48392 page52image48552 page52image48712 page52image48872 page52image49032 page52image49192 page52image49352 page52image49512 page52image49672 page52image49832 page52image49992 page52image50152 page52image50312 page52image50472 page52image50632 page52image50792 page52image50952 page52image51112 page52image51272 page52image51432 page52image51592 page52image51752 page52image51912 page52image52072 page52image52232 page52image52392 page52image52552 page52image52712 page52image52872 page52image53032 page52image53192 page52image53352 page52image53512 page52image53672 page52image53832 page52image53992 page52image54152 page52image54312 page52image54472 page52image54632 page52image54792 page52image54952 page52image55112 page52image55272 page52image55432 page52image55592 page52image55752 page52image55912 page52image56072 page52image56232 page52image56392 page52image56552 page52image56712 page52image56872 page52image57032 page52image57192 page52image57352 page52image57512 page52image57672 page52image57832 page52image57992 page52image58152 page52image58312 page52image58472 page52image58632 page52image58792 page52image58952 page52image59112 page52image59272 page52image59432 page52image59592 page52image59752 page52image59912 page52image60072 page52image60232 page52image60392 page52image60552 page52image60712 page52image60872 page52image61032 page52image61192 page52image61352 page52image61512 page52image61672 page52image61832 page52image61992 page52image62152 page52image62312 page52image62472 page52image62632 page52image62792 page52image62952 page52image63112 page52image63272 page52image63432 page52image63592 page52image63752 page52image63912 page52image64072 page52image64232 page52image64392 page52image64552 page52image64712 page52image64872 page52image65032 page52image65192 page52image65352 page52image65512 page52image65672 page52image65832 page52image65992 page52image66152 page52image66312 page52image66472 page52image66632 page52image66792 page52image66952 page52image67112 page52image67272 page52image67432 page52image67592 page52image67752 page52image67912 page52image68072 page52image68232 page52image68392 page52image68552 page52image68712 page52image68872 page52image69032 page52image69192 page52image69352 page52image69512 page52image69672 page52image69832 page52image69992 page52image70152 page52image70312 page52image70472 page52image70632 page52image70792 page52image70952 page52image71112 page52image71272 page52image71432 page52image71592 page52image71752 page52image71912 page52image72072 page52image72232 page52image72392 page52image72552 page52image72712 page52image72872 page52image73032 page52image73192 page52image73352 page52image73512 page52image73672 page52image73832 page52image73992 page52image74152 page52image74312 page52image74472 page52image74632 page52image74792 page52image74952 page52image75112 page52image75272 page52image75432 page52image75592 page52image75752 page52image75912 page52image76072 page52image76232 page52image76392 page52image76552 page52image76712 page52image76872 page52image77032 page52image77192 page52image77352 page52image77512 page52image77672 page52image77832 page52image77992 page52image78152 page52image78312 page52image78472 page52image78632 page52image78792 page52image78952 page52image79112 page52image79272 page52image79432 page52image79592 page52image79752 page52image79912 page52image80072 page52image80232 page52image80392 page52image80552 page52image80712 page52image80872 page52image81032 page52image81192 page52image81352 page52image81512 page52image81672 page52image81832 page52image81992 page52image82152 page52image82312 page52image82472 page52image82632 page52image82792 page52image82952 page52image83112 page52image83272 page52image83432 page52image83592 page52image83752 page52image83912 page52image84072 page52image84232 page52image84392 page52image84552 page52image84712 page52image84872 page52image85032 page52image85192 page52image85352 page52image85512 page52image85672 page52image85832 page52image85992 page52image86152 page52image86312 page52image86472 page52image86632 page52image86792 page52image86952 page52image87112 page52image87272 page52image87432 page52image87592 page52image87752 page52image87912 page52image88072 page52image88232 page52image88392 page52image88552 page52image88712 page52image88872 page52image89032 page52image89192 page52image89352 page52image89512 page52image89672 page52image89832 page52image89992 page52image90152 page52image90312 page52image90472 page52image90632 page52image90792 page52image90952 page52image91112 page52image91272 page52image91432 page52image91592 page52image91752 page52image91912 page52image92072 page52image92232 page52image92392 page52image92552 page52image92712 page52image92872 page52image93032 page52image93192 page52image93352 page52image93512 page52image93672 page52image93832 page52image93992 page52image94152 page52image94312 page52image94472 page52image94632 page52image94792 page52image94952 page52image95112 page52image95272 page52image95432 page52image95592 page52image95752 page52image95912 page52image96072 page52image96232 page52image96392 page52image96552 page52image96712 page52image96872 page52image97032 page52image97192 page52image97352 page52image97512 page52image97672 page52image97832 page52image97992 page52image98152 page52image98312 page52image98472 page52image98632 page52image98792 page52image98952 page52image99112 page52image99272 page52image99432 page52image99592 page52image99752 page52image99912 page52image100072 page52image100232 page52image100392 page52image100552 page52image100712 page52image100872 page52image101032 page52image101192 page52image101352 page52image101512 page52image101672 page52image101832 page52image101992 page52image102152 page52image102312 page52image102472 page52image102632 page52image102792 page52image102952 page52image103112 page52image103272 page52image103432 page52image103592 page52image103752 page52image103912 page52image104072 page52image104232 page52image104392 page52image104552 page52image104712 page52image104872 page52image105032 page52image105192 page52image105352 page52image105512 page52image105672 page52image105832 page52image105992 page52image106152 page52image106312 page52image106472 page52image106632 page52image106792 page52image106952 page52image107112 page52image107272 page52image107432 page52image107592 page52image107752 page52image107912 page52image108072 page52image108232 page52image108392 page52image108552 page52image108712 page52image108872 page52image109032 page52image109192 page52image109352 page52image109512 page52image109672 page52image109832 page52image109992 page52image110152 page52image110312 page52image110472 page52image110632 page52image110792 page52image110952 page52image111112 page52image111272 page52image111432 page52image111592 page52image111752 page52image111912 page52image112072 page52image112232 page52image112392 page52image112552 page52image112712 page52image112872 page52image113032 page52image113192 page52image113352 page52image113512 page52image113672 page52image113832 page52image113992 page52image114416 page52image114576 page52image114736 page52image114896 page52image115056 page52image115216 page52image115376 page52image116136 page52image116296 page52image116456 page52image116616
Residential Care Facilities Presentation Handout 52 June 1, 2011
Occupancy
Construction
Smoke Barrier
Sprinkler System
Smoke Alarms
Fire Alarm System
# of Exits
Rated Corridors
Delayed Egress
Bed- ridden
Exit Tactile Signs Exit
Emergency Lights
Fire Exiting
R-2.1
Rated
Yes
Yes
Yes
Manual & Auto. System
Two
Yes
Yes
Yes
Yes Yes
Yes
Yes
7+ non- Ambs or bed- ridden
CBC- 425.4.1& Table 503
CBC
1006.3
R-4
Non-rated up to 7,000 sq. feet
Yes
Yes
Yes
Manual & Auto. System
Two
Yes
Yes
Yes
Yes Yes
Yes
Yes
7+ ambs (May have 6 non- ambs
If > than 6,000 sq. ft. CBC 425.5.1 425.5.2
CBC 903.2.8 See Except.
CBC 425.7.3
CBC 425.8.2.1
If 11+ Occupants
Must meet all req. of
Upto6 Allowed.
1011.1 CBC 1011.3
CBC 1006.3
CFC 906.1
Or 6 bedridden)
R-3.1
Non-Rated
No
No- if only 1 bedridden
Yes
No
Two
No
Yes
Yes
No No
No
Yes
6 or less Regardless of ambulatory status
See special considerations in CB 425.3.2
CBC 907.2.11.2 & 907.2.11.2.2
CBC 1011.1
CFC 906.1 #1
CBC Table 503
See CBC 420.4.1 For Carbon Monoxide alarms
CBC 907.2.10.1 & 907.2.10.2
CBC Table 1018.1
CBC 1008.1.9.7
See exc.
See language in CBC 425.3.3 and 425.3.4
CBC 310.1
CBC Table 503
Strobes required in protective social care facilities housing any deaf person CBC 907.5.2.3.5
CBC 425.8.2.1 See exiting provisions of CBC 425.8.3.2 & 425.8.3.3 For exiting from
client
sleeping rooms.
Must meet all req. of CBC 1008.1.9.7
Hospice Can have Up to six. Others can have 1 if non- sprinklered And6If sprinklered.
If > than 6,000 sq. ft.
CBC 903.2.8
CBC 425.8.2.1
CBC 425.8.4.1 Table 1017.1
Must meet all req. of CBC 1008.1.9.7
CBC 310.1
1011.1 CBC 1011.3
CBC
CFC 906.1
CBC 425.5.1 425.5.2
See CBC 420.4.1 For Carbon Monoxide alarms
See Exc.
60” for non- ambs and 44”
for ambs CBC 425.8.4.2

See provisions of CBC 425.8.3.3
See CBC 420.4.1 for Carbon Monoxide alarms
425.7.3
CBC 907.2.6.1.1
Floor level- CBC 1011.6
2010 CBC & CFC Residential Care Facility Requirements (24 hour care only)
June 1, 2011

See except.
See provisions
of CBC 425.8.3.3
Exit path Marking CBC 1011.7
Signs
See exc. 

1 comment:

  1. Is an online gaming site that jackpot brings together more than 100 games, including online slot machines, Online Casino games and more. look new games This website is focused on rebate for additional and outmoded players. Because casino websites are legal, we have a strong financial foundation. And have a news system safe tolerable to be trusted by all members. https://918kiss2020.com/tag/jackpot/

    ReplyDelete

Thank you for commenting, please be advised as soon as your comments are read, we will be posting them to our blog. If your comment has nothing to bring and shed professional knowledge of the subject matter, more than likely it will be denied for posting. We serve the right to deny any comment that is not appropriate to our content.